16 

Bulk Protection 

When this setting is ‘on’, the bulk charging time is limited to 10 hours. A longer charging time 

could indicate a system error (e.g. a battery cell short-circuit). Not adjustable with DIP 

switches. 

 

AC input current limit 

These are the current limit settings at which PowerControl and PowerAssist come into 

operation. The factory setting is 12A. 

See Section 2 of the book 'Energy Unlimited’ or the many descriptions of this unique feature 

on our website www.victronenergy.com. 

Remark: lowest allowable current setting for PowerAssist: 2,7A. 

(2,7A per unit in case of parallel operation) 

 

UPS feature 

If this setting is ‘on’ and AC on the input fails, the MultiPlus switches to inverter operation 

practically without interruption. The MultiPlus can therefore be used as an Uninterruptible 

Power Supply (UPS) for sensitive equipment such as computers or communication systems. 

The output voltage of some small generator sets is too unstable and distorted for using this 

setting* – the MultiPlus would continually switch to inverter operation. For this reason, the 

setting can be turned off. The MultiPlus will then respond less quickly to AC input voltage 

deviations. The switchover time to inverter operation is consequently slightly longer, but most 

equipment (most computers, clocks or household equipment) is not adversely impacted. 

Recommendation: Turn the UPS feature off if the MultiPlus fails to synchronise or continually 

switches back to inverter operation. 

 

*In general, the UPS setting can be left ‘on’ if the MultiPlus is connected to a generator with a 

‘synchronous AVR regulated alternator’. 

The UPS mode may have to be set to ‘off’ if the MultiPlus is connected to a generator with a 

‘synchronous capacitor regulated alternator’ or an asynchronous alternator. 

 

Dynamic current limiter 

Intended for generators, the AC voltage is being generated by means of a static inverter (so-

called ‘inverter’ generators). In these generators, rpm is down-controlled if the load is low: this 

reduces noise, fuel consumption and pollution. A disadvantage is that the output voltage will 

drop severely or even completely fail in the event of a sudden load increase. More load can 

only be supplied after the engine is up to speed. 

If this setting is ‘on’, the MultiPlus will start supplying extra power at a low generator output 

level and gradually allow the generator to supply more, until the set current limit is reached. 

This allows the generator engine to get up to speed. 

This setting is also often used for ‘classic’ generators that respond slowly to sudden load 

variation. 

Summary of Contents for EasySolar 12/1600/70

Page 1: ...Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Manuale IT Appendix EasySolar 12 1600 70 16 230V MPPT 100 50 24 1600 40 16 230V MPPT 100 50 ...

Page 2: ...of gas or dust explosions Consult the battery manufacturer s information to ascertain that the product is intended for use in conjunction with the battery Always comply with the battery manufacturer s safety instructions WARNING Do not lift heavy loads without assistance Installation Read the installation instructions in the installation manual before installing the equipment This is a Safety Clas...

Page 3: ... 2 1 General All in one solar power solution The EasySolar combines a MPPT solar charge controller an inverter charger and AC distribution in one enclosure The product is easy to install with a minimum of wiring Solar charge controller BlueSolar MPPT 100 50 Up to three strings of PV panels can be connected with three sets of MC4 PV ST01 PV connectors Inverter charger MultiPlus Compact 12 1600 70 o...

Page 4: ...ty of shore or generator power This feature takes the principle of PowerControl to a further dimension allowing the MultiPlus Compact to supplement the capacity of the alternative source Where peak power is so often required only for a limited period it is possible to reduce the size of generator needed or conversely enable more to be achieved from the typically limited shore connection When the l...

Page 5: ...To learn more about batteries and charging batteries please refer to our book Electricity on Board available free of charge from Victron Energy and downloadable from www victronenergy com For more information about adaptive charging please look under Technical Briefs on our website 2 4 Charge Controller MPPT 100 50 Charge current up to 50A and PV voltage up to 100V The BlueSolar MPPT 100 50 charge...

Page 6: ... setting the controller switches to constant voltage mode When only shallow discharges occur the absorption time is kept short in order to prevent overcharging of the battery After a deep discharge the absorption time is automatically increased to make sure that the battery is completely recharged Additionally the absorption period is also ended when the charge current decreases to less than 2A Fl...

Page 7: ...es from running flat 3 2 Remote control Remote control is possible with a 3 way switch or with a Digital Multi Control panel The Control panel has a simple rotary knob with which the maximum current of the AC input can be set see PowerControl and PowerAssist in Section 2 For the appropriate DIP switch settings see sect 5 5 1 3 3 Equalisation and forced absorption 3 3 1 Equalisation Traction batter...

Page 8: ... leave the switch in this position for to 2 seconds b Switch rapidly back from charger only to on and leave the switch in this position for to 2 seconds c Switch once more rapidly from on to charger only and leave the switch in this position 4 On the MultiPlus the three LEDs Inverter Charger and Alarm will now flash 5 times If a MultiControl panel is connected on the panel the LEDs bulk absorption...

Page 9: ... on and supplies power to the load Pre alarm overload or battery voltage low or inverter temperature high inverter on charger off alarm charger only The inverter is switched off Alarm overload or battery voltage low or inverter temperature high or DC ripple voltage on battery terminal was too high inverter on charger off alarm charger only LED off LED flashes LED illuminated ...

Page 10: ...ugh and the charger is switched off The battery charger can not reach battery end voltage bulk protection mode inverter on charger off alarm charger only The AC input voltage is switched through and the charger operates in bulk or absorption mode inverter on charger off alarm charger only The AC input voltage is switched through and the charger operates in float mode inverter on charger off alarm ...

Page 11: ...d be installed in a heat resistant environment if it is used with equipment where a substantial amount of power is to be converted You should prevent the presence of e g chemicals synthetic components curtains or other textiles etc in the immediate vicinity 4 2 Connection of Battery cables see appendix A In order to fully utilize the full capacity of the product batteries with sufficient capacity ...

Page 12: ...nnectors into the AC out connector AC0 to AC3 from left to right side Use an insulated box spanner in order to avoid shorting the battery Avoid shorting the battery cables This is a Safety Class I product supplied with a protective grounding terminal Uninterruptible protective grounding must be provided at the AC input and or output terminals and or chassis grounding point located externally on th...

Page 13: ...2 0 12 5 13 0 13 5 14 0 14 5 15 0 0 5 10 15 20 25 30 35 40 45 50 55 60 Battery temperature Volts 20 21 22 23 24 25 26 27 28 29 30 Volts 4 4 3 Remote Control panel remote on off switch The product can be remotely controlled in two ways With an external 3 way switch With a Multi Control Panel Please see section 5 5 1 for appropriate DIP switch settings Only one remote control can be connected i e ei...

Page 14: ...e curve four stage adaptive with BatterySafe mode Charge current 75 of the maximum charge current Victron Gel Deep Discharge also suitable for Victron AGM Deep Discharge Automatic equalisation charging off Absorption voltage 14 4 28 8V Absorption time up to 8 hours depending on bulk time Float voltage 13 8 27 6V Storage voltage 13 2 26 4V not adjustable Repeated absorption time 1 hour Absorption r...

Page 15: ... input voltage The output voltage is then equal to the input voltage Adjustability Lower limit 180 230V Upper limit 230 270V Inverter voltage Output voltage of the MultiPlus in battery operation Adjustability 210 245V Search Mode Applicable in stand alone configuration only If search mode is on the power consumption in no load operation is decreased by approx 70 In this mode the Compact when opera...

Page 16: ...el Exide A200 and tubular plate stationary batteries OPzS This setting can also be used for many other batteries e g Victron AGM Deep Discharge and other AGM batteries and many types of flat plate open batteries Four charging voltages can be set with DIP switches Automatic equalisation charging This setting is intended for tubular plate traction batteries During absorption the voltage limit increa...

Page 17: ...hover time to inverter operation is consequently slightly longer but most equipment most computers clocks or household equipment is not adversely impacted Recommendation Turn the UPS feature off if the MultiPlus fails to synchronise or continually switches back to inverter operation In general the UPS setting can be left on if the MultiPlus is connected to a generator with a synchronous AVR regula...

Page 18: ...g signal 5 3 Configuration by computer All settings can be changed by means of a computer Some settings can be changed with DIP switches see Section 5 2 For changing settings with the computer the following is required VEConfigureII software or the appropriate Assistant s can be downloaded free of charge at www victronenergy com A RJ45 UTP cable and the MK2 2b RS485 to RS232 interface If the compu...

Page 19: ...in inverter mode b Set the DIP switches as required c Store the settings by moving DIP switch 8 to on and back to off 5 5 1 DIP switch 1 and 2 Default setting to operate the product with the On Off Charger Only switch ds 1 off ds 2 on The default setting is required when using the On Off Charger Only switch in the front panel Setting for remote operation with a Multi Control Panel ds 1 on ds 2 off...

Page 20: ...mode AGM spiral cell ds3 on ds4 on 15 0 30 0 60 0 13 8 27 6 55 2 13 2 26 4 52 8 6 Tubular plate or OPzS batteries in cyclic mode Batteries with high antimony content can typically be charged with a lower absorption voltage than batteries with low antimony content Please refer to our book Electricity on Board downloadable from our website www victronenergy com for details and suggestions about char...

Page 21: ... panel or remote switch connected 2 No panel or remote switch connected 3 4 GEL 14 4V 5 Frequency 50Hz 6 Search mode off 7 AC in Limit 12Amp 8 Store setting off on off Example 2 1 No panel or remote switch connected 2 No panel or remote switch connected 3 4 AGM 14 7V 5 Frequency 50Hz 6 Search mode off 7 AC in Limit 4Amp 8 Store setting off on off Example 3 1 Panel or remote switch connected 2 Pane...

Page 22: ...larm LED flashes Pre alarm alt 1 The DC input voltage is low Charge the battery or check the battery connections The alarm LED flashes Pre alarm alt 2 The ambient temperature is too high Place the inverter in a cool and well ventilated room or reduce the load The alarm LED flashes Pre alarm alt 3 The load on the inverter is higher than the nominal load Reduce the load The alarm LED flashes Pre ala...

Page 23: ...e Inverter is damaged The battery is overcharged The absorption voltage has been set to an incorrect value Adjust the absorption voltage to the correct value The float voltage has been set to an incorrect value Adjust the float voltage to the correct value A defective battery Replace the battery The battery is too small Reduce the charging current or use a battery with a higher capacity The batter...

Page 24: ...ve mentioned conditions For example 24V battery and mono or polycristalline panels Minimum number of cells in series 72 2x 12V panel in series or 1x 24V panel Maximum 144 cells Remark at low temperature the open circuit voltage of a 144 cell solar array may exceed 100V depending on local conditions and cell specifications In that case the number of cells in series must be reduced 7 3 Cable connect...

Page 25: ...Marine flooded Rolls Solar flooded 28 6 27 6 32 2 Default setting Gel Victron deep discharge Gel Exide A200 AGM Victron deep discharge Stationary tubular plate OPzS Rolls Marine flooded Rolls Solar flooded 28 8 27 6 32 3 AGM spiral cell Stationary tubular plate OPzS Rolls AGM 29 4 27 6 32 4 PzS tubular plate traction batteries or OPzS batteries 29 8 27 6 32 5 PzS tubular plate traction batteries o...

Page 26: ...n will be on when the absorption voltage is reached Switches off at the end of the absorption period Blue LED float will be on after the solar charger has switched to float 8 2 Battery charging information The charge controller starts a new charge cycle every moring when the sun starts shining The maximum duration of the absorption period is determined by the battery voltage measured just before t...

Page 27: ...daily absorption charging when the system operates without load or with a small load 8 3 Connectivity Several parameters can be customized VE Direct to USB cable ASS030530000 and a computer needed See the data communication whitepaper on our website The required software can be downloaded from http www victronenergy nl support and downloads software The charge controller can be connected to a Colo...

Page 28: ...itions are equal for charger and battery Only for a 24V system wrong system voltage chosen 12V instead of 24V by the charge controller Disconnect PV and battery after making sure that the battery voltage is at least 19V reconnect properly reconnect battery first The battery is being overcharged A battery cell is defect Replace battery Large ambient temperature difference between charger and batter...

Page 29: ...C Input Input voltage range 187 265 VAC Input frequency 45 65 Hz Power factor 1 Charge voltage absorption 14 4 28 8V Charge voltage float 13 8 27 6V Storage mode 13 2 26 4V Charge current house battery 4 70A 40A Battery temperature sensor yes Programmable relay 5 yes Protection 2 a g Solar Charge Controller Maximum battery current 50A Maximum PV power 6a b 700W 1400W Maximum PV open circuit voltag...

Page 30: ...r will limit input power to 720W resp 1440W 6b PV voltage must exceed Vbat 5V for the controller to start Thereafter minimum PV voltage is Vbat 1V Common Characteristics Operating temp range 20 to 50 C fan assisted cooling Humidity non condensing max 95 ENCLOSURE Material Colour aluminium blue RAL 5012 Protection category IP21 Battery connection Battery cables of 1 5 meter PV connection Three sets...