3. Installation

3.1. Installation Considerations

Ensure that the Autotransformer is used under the correct operating conditions. Never operate it in a wet or dusty environment.
The AT is rated to IP21.

Ensure that there is always sufficient free space around the product for ventilation (10cm or 4 inches), and that ventilation
openings are not blocked. See specification table for dimensions in Section 4.

Install the product in a heatproof environment. Ensure therefore that there are no chemicals, plastic parts, curtains or other
textiles, etc. in the immediate vicinity of the equipment.

3.2. Mounting

Using a level if needed, install the wall hanger in the desired position with provided fasteners. Place AT on to wall hanger and pull
down to achieve a snug fit. Install fasteners in the 2 holes provided at the lower portion of the enclosure.

The AT can be mounted in any orientation. Note that the Vertical position is the optimal orientation because it has maximum heat
dissipation and easy access the terminal board.

3.3. Wiring

The Autotransformer has several possible configuration options and must therefore be installed correctly for the desired outcome.
The terminal block may be used as an input for certain applications, and in other applications the terminal block is used as output.

Remove cover by removing 4 fasteners found in all four corners. Carefully remove front cover keeping in mind the 3 LED status
lights.

See diagrams in Sections 2.3.1 through 2.3.4 for the placement of conductors that correspond with the desired configuration.

3.4. Conduit

Both models of the AT can be fitted with conduit if required. For the 32A model remove supplied cable glands/strain relief and
replace with 1/2” (.5 inch) or ¾” (.75 inch) NPT (National Pipe Thread) conduit fittings. See illustration below. The 100A model will
require lager conduit fittings.

Victron Energy Autotransformer

Page 9

Installation

Summary of Contents for Buck-Boost 100A

Page 1: ...Victron Energy Autotransformer 32 A and 100 A Rev 01 06 2022 ENGLISH...

Page 2: ...Up Voltage 4 2 3 3 Stepping Down Voltage 5 2 4 Ground Relay 7 2 5 Temperature Protected 7 2 6 Over Current Protection 8 2 7 Sizing Limitations 8 3 Installation 9 3 1 Installation Considerations 9 3 2...

Page 3: ...uce the chance of electrical shock or accidental short circuits Select the wire size based on the protection provided by the circuit breakers Before making any connections verify that the circuit brea...

Page 4: ...cifications 2 2 Models 120 240V 32A 120 240V 100A Pass through current is 32A and 100A respectively the transformers are 100 equal in both models See more information in section 2 8 2 3 Types of Use 2...

Page 5: ...See diagram below for wiring instructions Victron Energy Autotransformer Page 3 Introduction...

Page 6: ...ot what is needed in the installation the autotransformer can create the needed voltage by doubling the incoming voltage The alternative to stacking two 120Vac inverters to provide a 120 240Vac Split...

Page 7: ...e autotransformer makes it possible to use all available power from both legs of the generator to power loads and to charge batteries When the available AC power source is not what is needed in the in...

Page 8: ...Victron Energy Autotransformer Page 6 Introduction...

Page 9: ...al block in Multi Quattro and Earth terminal block in Autotransformer by Positive and Negative conductors In some of the diagram examples in Section 2 4 1 through 2 4 3 it is mentioned when it is poss...

Page 10: ...in two models a 32A model and a 100A model This value is defined in the amount of current there can be in pass through so in other words the current which is forwarded without being converted The tran...

Page 11: ...can be mounted in any orientation Note that the Vertical position is the optimal orientation because it has maximum heat dissipation and easy access the terminal board 3 3 Wiring The Autotransformer...

Page 12: ...rrent 32A 100 A Neutral Current 30 min 32A 3800 VA Neutral Current Continuous 28A 40 C 100 F Transformer Type Toroidal Enclosure Aluminum Input Circuit Breaker Yes Electrical Terminals Screw Terminals...

Page 13: ...0 10 53 103 153 12 17 6 4 5x Dimensions in mm Dimension Drawing Autotransformer ITR000100001 Autotransformer 120 240VAC 32A ITR000100101 Autotransformer 120 240VAC 100A D E F C 1 2 3 4 B A 3 2 1 5 C D...

Page 14: ...unreasonable use or misuse neglect exposure to excess moisture fire improper packing lightning power surges or other acts of nature This limited warranty does not cover damage deterioration or malfun...

Reviews: