![Victron energy Buck-Boost 100A Manual Download Page 10](http://html1.mh-extra.com/html/victron-energy/buck-boost-100a/buck-boost-100a_manual_1014930010.webp)
2.6. Over Current Protection
In case of over current the MCB will switch off. Disconnect some of the load.
The MCB is for Over Current and Temperature Protection and switching the unit ON/OFF.
2.7. Sizing Limitations
The Autotransformer comes in two models, a 32A model and a 100A model. This value is defined in the amount of current there
can be in pass through, so in other words the current which is forwarded without being converted. The transformer itself is equal
in both models and has a 32A capacity (peak) and 28A nominal. This is the maximal current that can be used to transfer energy
from leg to leg or from 120Vac to 240Vac.
Victron Energy Autotransformer
Page 8
Introduction