2.2    Charge Efficiency Factor (CEF) 
 
Not all energy transferred into the battery during battery charging, is 
available during discharge of the battery. The charge efficiency of a 
brand new battery is approximately 90%, meaning that 10Ah must be 
transferred to the battery to get 9Ah actually stored in the battery. This 
efficiency figure is called Charge-Efficiency-Factor (CEF) and will 
decrease with battery age. The BMV-501 can automatically calculate the 
CEF of the battery. 
 
2.3    Peukert’s exponent 
 
As mentioned earlier in chapter 1.2 the Peukert efficiency describes how 
if you discharge a battery faster than the 20hr rating, it’s Amphour 
capacity decreases. The amount of battery capacity reduction is called 
‘Peukert exponent’ and can be adjusted from 

1.00

 to 

1.50

 in Function 

F10. The higher the Peukert exponent the faster the battery size shrinks 
with increasing discharge rate. An ideal (theoretical) battery has a 
Peukert Exponent of 1.00 and doesn’t care how big the discharge current 
is. Of course such batteries do not exist, and an F10 setting of 

1.00

 is 

only implemented to bypass Peukert compensation in the BMV-501. 
 
The default setting for the Peukert exponent is 1.25, and is an 
acceptable average value for most lead acid type of batteries. However 
for precise battery monitoring, entering the right Peukert exponent is 
essential. If the Peukert exponent is not provided with your battery, you 
can calculate it by using other specifications which must be provided with 
your battery. The Peukert equation is stated below : 
 

Cp = I

n

t  where Peukert exponent ‘n’ = 

2

log

1

log

1

log

2

log

I

I

t

t

 

 
The battery specifications needed for calculation of the Peukert 
exponent, are the rated battery capacity (usually the 20hr discharge 
rate

(1)

 ) and for example a 5hr discharge rate

(2)

. See the calculation 

example below to define the Peukert exponent using these two 
specifications : 
 
  5hr rating,    C5  =  75Ah 
           

  t1   =  5hr 

           

  I1   =  75Ah/5hr = 15A 

 

Summary of Contents for BMV-501

Page 1: ...USER MANUAL GEBRUIKSAANWIJZING Battery monitor BMV 501 Batterij monitor BMV 501 victron energy victron energy victron energy victron energy ...

Page 2: ...R SPECIAL COLLATERAL INCIDENTAL OR CONSEQUENTIAL DAMAGES IN CONNECTION WITH OR ARISING OUT OF PURCHASE OR USE OF THESE VICTRON ENERGY PRODUCTS THE SOLE AND EXCLUSIVE LIABILITY TO VICTRON ENERGY B V REGARDLESS OF THE FORM OF ACTION SHALL NOT EXCEED THE PURCHASE PRICE OF THE VICTRON ENERGY PRODUCTS DESCRIBED HERE IN For conditions of use and permission to use this manual for publication in other tha...

Page 3: ...3 SECTIONS Page English 4 Nederlands 25 ...

Page 4: ...re there are no permanent sources of mains power An automatic stand alone power system can be created with a configuration comprising of a Victron Energy inverter battery charger and last but not least batteries with sufficient capacity Our equipment is suitable for countless situations in the field on ships or other places where a mobile 230 VoltAC power supply is indispensable Victron Energy has...

Page 5: ... working with batteries 8 2 2 Charge Efficiency Factor CEF 9 2 3 Peukert s exponent 9 2 4 Charged parameters 11 2 5 Synchronizing the BMV 501 11 2 6 Function overview 12 3 GENERAL OPERATION 17 4 ADVANCED FEATURES 19 4 1 Historic data 19 4 2 PC link 19 4 3 Super lock 20 5 TROUBLESHOOTING GUIDE 20 5 1 Warranty 22 6 TECHNICAL DATA 22 6 1 Declaration of conformity 24 ...

Page 6: ...rrent of 5Amps for a period of 20hours is rated at 100Ah 5 20 100 The BMV 501 continuously measures the nett current flow in or out of the battery so it can calculate the amount of energy removed from or added to the battery But since battery age discharge current and temperature all influence the battery s capacity you can t rely simply on an Amp hours reading When the same 100Ah battery is disch...

Page 7: ... guide only We always encourage the use of the state of charge readout for accurate battery monitoring Besides the main function of the BMV 501 displaying the actual battery status this monitor offers many other features The readout of actual battery voltage current and temperature with optional temperature sensor the ability to store historic data the PC computer link and the Super lock function ...

Page 8: ...Batteries can generate explosive gases during operation Never smoke or allow a spark or flame in the vicinity of a battery Provide sufficient ventilation around the battery 2 Wear eye and clothing protection Avoid touching eyes while working near batteries Wash your hands when done 3 If battery acid contacts skin or clothing wash immediately with soap and water If acid enters eye immediately flood...

Page 9: ...increasing discharge rate An ideal theoretical battery has a Peukert Exponent of 1 00 and doesn t care how big the discharge current is Of course such batteries do not exist and an F10 setting of 1 00 is only implemented to bypass Peukert compensation in the BMV 501 The default setting for the Peukert exponent is 1 25 and is an acceptable average value for most lead acid type of batteries However ...

Page 10: ... which represents the rated battery capacity in most cases 1 This second rating can be defined by discharging a fully charged battery with a constant current until the battery reaches 1 75V per cell is 10 5V for a 12V battery or 21V for a 24V battery a calculation example is shown below A 200Ah battery is discharged with a constant current of 20A and after 8 5 hours 1 75V cell is reached So t1 8 5...

Page 11: ...y fully charging the battery When the charger is operating in the float stage the charger considers the battery full At this moment the BMV 501 must reckon the battery as full too so that the Amphour counting can be reset to zero and the state of charge reading set to 100 0 By precisely adjusting the charged parameters in the BMV 501 the battery monitor can automatically synchronize with the charg...

Page 12: ... desired Function can be selected The selected Function is represented as Fxx where xx indicates the Function number The and keys can be used to alter the value of the selected Function By pressing the SETUP key again the next Function will be selected To save the changed settings to the BMV 501 memory the SETUP key must be pressed for three seconds until the display stops flashing and the battery...

Page 13: ...ttery can be considered as fully charged Make sure the current charged parameter is always greater than the minimum current at which the charger maintains the battery or stops charging Default 2 0 Range 0 5 10 0 Stepsize 0 5 F04 Charged parameter time This is the time the charged parameters as described in F02 and F03 must be met in order to consider the battery as fully charged Default 4 minutes ...

Page 14: ...s above this value after 5 seconds the message Hi shall appear on the display and the alarm relay will be activated Default 16 0V Range OFF 10 0 35 0V Stepsize 0 1V F09 Charge efficiency factor CEF It is recommended to keep this value at AU automatic calculation The value A90 resets the automatic calculation to 90 A manual setting is represented by Uxx where xx is the charge efficiency see chapter...

Page 15: ...cap C Stepsize 0 05 cap C F13 Time to go averaging period Specifies the time window in minutes that the moving averaging filter works with Selecting the right time depends on your installation A value of 0 disables the filter and gives you instantaneous real time readout however the displayed values may fluctuate heavily Selecting the highest time 12 minutes ensures that long term load fluctuation...

Page 16: ...ssing a key on the BMV 501 Furthermore settings can be made to leave the backlight always ON or always OFF In the setting AU the backlight will be activated automatically when the charge discharge current exceeds 1A or when a key is pressed Default 30 seconds Range OFF 10 60 ON AU Stepsize 10 seconds F18 Reserved Default F19 Firmware version Displays the firmware version of the BMV 501 No alterati...

Page 17: ...y sets this readout to 0 0Ah synchronized system When for three hours a current of 12Amps is drawn from the battery this readout gives 36 0Ah State of charge This is the best way to monitor the actual state of the battery This readout represents the current amount of energy left in the battery A fully charged battery sets this readout to 100 0 while a fully discharged battery is represented as 0 0...

Page 18: ...elow the adjusted discharge floor see Function F05 The battery needs to be recharged as soon as possible BATTERY FULL flashing The battery is fully charged and the battery charger is probably operates in the float stage The charger may be turned off The monitor is synchronized with the battery CHARGE BATTERY FULL flashing Charge the battery completely full This indication will arise when the BMV 5...

Page 19: ...rvoltage alarms H08 The number of overvoltage alarms H09 reserved H10 reserved The information stated above can be recalled in the history readout This readout can be activated by pressing all three keys of the BMV 501 for five seconds After this five seconds a flashing H01 shall appear on the display With the and selection keys the value of H01 can be displayed By pressing the SETUP next key the ...

Page 20: ...wo is that the setup lock can be disabled by anybody even without communication between BMV 501 and PC The setup lock is used to avoid accidental alteration of the Function values The super lock however can only be de activated via the PC link using a unique password The super lock feature is primarily meant for warranty purposes 5 TROUBLESHOOTING GUIDE PROBLEM REMEDY OR SUGGESTION The monitor doe...

Page 21: ...arge and or time to go readout not accurate Check if all current is flowing through the shunt the negative terminal of the battery may only contain the wire going to the battery side of the shunt Current sense leads from the shunt are reversed Check battery capacity in Function F01 Check CEF in Function F09 Check Peukert Exponent in Function F10 Check Battery temperature in Function F11 Check Temp...

Page 22: ...than Victron Energy B V qualified personnel Victron Energy B V is not responsible for any loss damage or costs arising from improper use use in an unsuitable environment or improper installing and user setup of the battery monitor 6 TECHNICAL DATA BMV 501 TECHNICAL DATA Supply voltage range 9 35VDC Supply current Vin 24VDC without BL 6mA Vin 12VDC without BL 8mA Input voltage range 0 35VDC Input c...

Page 23: ...current shunt this user manual installation guide self adhesive drill mould Accessories BMV 501 Connection kit art ASS030077000 length 10m art ASS030078000 length 15m art ASS030079000 length 20m art ASS030080000 length 30m BMV 501 temperature sensor art ASS030081000 length 10m art ASS030082000 length 20m art ASS030083000 length 30m BMV 501 communications interface kit art ASS030084000 BMV 501 Ethe...

Page 24: ...itor BRAND Victron Energy MODEL BMV 501 Conforms to the requirements of the following Directive of the European Union EMC Directive 89 336 EEC The above product is in conformity with the following harmonized standards EN50081 1 1994 EMC Generic Emissions Standard EN50082 1 1997 EMC Generic Immunity Standard Signed R Vader Authority Managing Director Date 12 September 2002 ...

Page 25: ...sen Victron Energy levert kwalitatief hoogwaardige wisselstroomvoor zieningen voor gebruik op plaatsen waar geen permanente aansluiting op het elektriciteitsnet 230 Vac voorhanden is Met behulp van de apparatuur van Victron Energy kan een automatisch stand alone energievoorzieningsysteem worden gecreëerd Maak voor de configuratie naast krachtige accu s gebruik van een omvormer en een acculader De ...

Page 26: ...het werken met accu s 30 2 2 Laadrendement CEF 31 2 3 Peukert s exponent 31 2 4 Laadfactoren Charged parameters 33 2 5 Het synchroniseren van de BMV 501 33 2 6 Function overzicht 34 3 ALGEMENE BEDIENING 39 4 GEAVANCEERDE EIGENSCHAPPEN 41 4 1 Historische data 41 4 2 PC link 41 4 3 Super lock 42 5 STORINGSTABEL 42 5 1 Garantie 44 6 TECHNISCHE SPECIFICATIES 44 6 1 Conformiteitsverklaring 47 ...

Page 27: ... uren of Amphours kortweg Ah Een batterij welke in staat is een stroom van 5A voor een periode van 20 uur te leveren wordt een capaciteit toegekend van 100Ah De BMV 501 meet continu de huidige stroomsterkte die in of uit de batterij vloeit en berekent hieruit de hoeveelheid afgenomen of toegevoegde energie Maar omdat de leeftijd de ontlaadstroom en de temperatuur van de batterij de capaciteitswaar...

Page 28: ... de belasting erg fluctueert is het raadzamer om de state of charge uitlezing te gebruiken vanwege het momentele karakter van de time to go uitlezing Naast de hoofdfunktie van de BMV 501 het weergeven van de actuele batterij status is deze tot nog veel meer in staat Het uitlezen van actuele batterij spanning stroom en temperatuur met optionele temperatuur sensor en zaken als het opslaan van bijzon...

Page 29: ...n Vermijd roken vonken of open vuur in de buurt van accu s Zorg voor voldoende ventilatie 2 Draag oog en kleding bescherming Vermijd het aanraken van de ogen wanneer er met accu s gewerkt wordt Was de handen na het werken met accu s 3 Als accuzuur in contact komt met de huid of kleding was dit dan onmiddellijk af met water en zeep Als het zuur in contact komt met de ogen spoel dan onmiddellijk met...

Page 30: ...he batterij heeft een Peukert exponent van 1 00 en is niet gevoelig voor de grootte van de ontlaadstroom Uiteraard bestaan deze batterijen niet en een F10 keuze van 1 00 is ook alleen maar geïmplementeerd om de Peukert compensatie eventueel uit te kunnen schakelen in de BMV 501 De standaard instelling voor de Peukert exponent is 1 25 en is een acceptabele gemiddelde waarde voor de meeste loodzwave...

Page 31: ...een tweede rating worden bepaald naast de C20 of C10 C5 1 rating die de nominale batterij capaciteit aangeeft Deze tweede rating kan bepaald worden door de volledig geladen batterij met een constante stroom te ontladen totdat er een celspanning van 1 75V is 10 5V voor een 12V batterij of 21V voor een 24V batterij is bereikt Een rekenvoorbeeld staat hieronder afgebeeld Een 200Ah batterij wordt ontl...

Page 32: ...e laden Wanneer de lader zich in de float fase bevindt wordt de batterij door de lader als vol beschouwd Er wordt dan namelijk niets meer bijgeladen Op dit moment moet de BMV 501 de batterij ook als vol beschouwen waarbij de Ampère uren telling op nul gezet wordt en de state of charge uitlezing op 100 0 Door de laadfactoren goed in te stellen in de batterij monitor kan deze zich nu automatisch syn...

Page 33: ...p de SETUP toets om de gewenste instelling te selecteren De geselecteerde instelling wordt weergegeven als Fxx waarbij xx het nummer van de instelling Function voorstelt Gebruik vervolgens de en toetsen om de geselecteerde instelling te wijzigen Door weer op de SETUP toets te drukken wordt de volgende instelling geselecteerd Om de gewijzigde instellingen op te slaan moet de SETUP toets weer drie s...

Page 34: ...ligt dan kan de batterij als vol beschouwd worden Zorg ervoor dat de stroom laadfactor altijd groter is dan de minimum stroom waarbij de lader stopt met laden of waarbij de lader de batterij onderhoudt in de float fase Standaard 2 0 Bereik 0 5 10 0 Stapgrootte 0 5 F04 Tijd laadfactor Tijd in minuten dat aan laadvoorwaarden van F02 en F03 moet worden voldaan om de batterij als vol te beschouwen Sta...

Page 35: ...econden op het display kenbaar gemaakt worden als Hi en zal het alarm relais geactiveerd worden Standaard 16 0V Bereik OFF 10 0 35 0V Stapgrootte 0 1V F09 Laadrendement instelling CEF Het wordt aanbevolen deze waarde op AU automatisch berekenen te laten staan De instelling A90 reset de automatische berekening naar 90 Een handmatige instelling wordt weergegeven als Uxx waarbij xx het laadrendement ...

Page 36: ... 05 cap C F13 Time to go averaging period Bepaalt het tijdsraam in minuten waar het schuivend gemiddelde filter mee werkt Een instelling van 0 schakelt het filter uit en geeft een momentele real time time to go uitlezing echter de waardes kunnen hevig fluctueren Door de hoogste tijd 12 minuten te selecteren wordt er rekening gehouden met lange termijn fluctuaties in de time to go uitlezing Standaa...

Page 37: ...het display uitgaat Tevens kan gekozen worden of de backlight altijd uit OFF of altijd aan ON staat Tenslotte is er nog de automatische mode AU waarbij de backlight automatisch aangaat als de laad ontlaad stroom groter is dan 1A of als er een toets ingedrukt wordt Standaard 30 seconden Bereik OFF 10 60 ON AU Stapgrootte 10 seconden F18 Gereserveerd Standaard F19 Firmware version Geeft de firmware ...

Page 38: ... 3 uur lang een stroom van 12A is gebruikt laat het display 36 0Ah zien Laadtoestand ook wel state of charge genoemd Dit is de beste manier om de laadtoestand van de batterij uit te lezen Het geeft de overgebleven hoeveelheid energie weer net als de brandstofmeter in een auto Een volledig geladen batterij geeft een 100 0 uitlezing en een volledig ontladen batterij wordt weergegeven als 0 0 Tijd no...

Page 39: ...ischarge floor zie Function F05 gedaald De batterij dient zo snel mogelijk geladen te worden BATTERY FULL knipperend De batterij is volledig geladen en de lader staat waarschijnlijk in de float fase De lader mag uitgeschakeld worden maar dit is niet noodzakelijk De monitor staat nu synchroon met de batterij CHARGE BATTERY FULL knipperend Laad de batterij volledig vol Deze indicatie wordt gegeven a...

Page 40: ...0 heeft bereikt H07 Het aantal keren dat het under voltage alarm is geactiveerd H08 Het aantal keren dat het over voltage alarm is geactiveerd H09 gereserveerd H10 gereserveerd Bovenstaande informatie is uit te lezen in de zogenaamde history readout Deze uitlezing kan worden geactiveerd door 5 seconden lang alle drie de bedieningstoetsen ingedrukt te houden Hierna zal H01 knipperend op het display...

Page 41: ...iden is dat de setup lock door elke gebruiker uitgezet kan worden ook als er geen communicatie met de PC plaatsvindt De setup lock dient er alleen voor om niet per ongeluk een instelling te kunnen veranderen Terwijl de super lock alleen via de PC link door de gebruiker met het wachtwoord uit te schakelen is en er voor dient dat er niets veranderd of gewist kan worden in verband met bijvoorbeeld ga...

Page 42: ...uitgeschakeld via de administrator software met behulp van de PC link CHARGE BATTERY of CHARGE BATTERY FULL blijft knipperen Laad de batterij volledig op synchroniseer uw batterij met de monitor Controleer de laadfactoren in de Functions F02 F03 en F04 voor mogelijk foute instellingen State of charge en of time to go uitlezing niet nauwkeurig Controleer of alle stroom wel via de shunt vloeit de mi...

Page 43: ...Gedurende deze periode neemt Victron Energy B V de kosten van eventuele reparatie voor zijn rekening Victron Energy B V is niet verantwoordelijk voor de transportkosten van de batterij monitor Deze garantie vervalt wanneer de batterij monitor fysiek beschadigd is zowel extern als intern als er iets aan het oorspronkelijke apparaat veranderd is of als de batterij monitor behuizing door een niet gem...

Page 44: ... Nauwkeurigheid spannings meting 0 3 Nauwkeurigheid stroommeting 0 4 Afmetingen frontpaneel 65 x 65mm behuizingsdiameter 52mm inbouwdiepte 72mm Netto gewicht BMV 501 70gram Shunt 315 gram Materiaal behuizing ABS stikker Polyester Uitgerust met Potentiaal vrij normally open alarm contact 60V 1A max Inhoud verpakking BMV 501 batterij monitor 500A 50mV stroom shunt veiligheidsvoorschriften deze gebru...

Page 45: ...0080000 lengte 30m BMV 501 temperatuur sensor art ASS030081000 lengte 10m art ASS030082000 lengte 20m art ASS030083000 lengte 30m BMV 501 communicate interface kit art ASS030084000 BMV 501 Ethernet kit art ASS030075000 1 5 spanningsdeler art ASS030076000 N B Bovenstaande gegevens kunnen zonder aankondiging van de fabrikant wijzigen ...

Page 46: ...ERIJ MONITOR MERK Victron Energy MODEL BMV 501 Conform de eisen zijn van de volgende Directive of the European Union EMC Directive 89 336 EEC Het bovenstaande product voldoet aan de volgende geharmoniseerde normen EN50081 1 1994 EMC Generic Emissions Standard EN50082 1 1997 EMC Generic Immunity Standard Getekend R Vader Functie Directeur Datum 12 september 2002 ...

Page 47: ...6 535 97 00 Customer support desk 31 0 36 535 97 77 General and Service fax 31 0 36 531 16 66 Sales fax 31 0 36 535 97 40 E mail sales victronenergy com Internet site http www victronenergy com Doc no ISM010030000 REV03 doc Date 29 11 2002 Dealer Stock number ...

Reviews: