INSTALLATION 

 

Your layout and particular hazards dictate the placement of fire extinguishers.    NFPA-10 requires that 

hand  portable  extinguishers  with  a  gross  weight  less  than  40  lbs.  be  hung  with  the  top  of  the 

extinguisher

  not  more

  than  5  ft.  (1.53  m)  above  the  floor.    Extinguishers  having  a  gross  weight 

greater than 40 lbs. (18.14 kg) should be installed so that the top of the extinguisher is 

not more 

than 3 

1/2 ft. (1.07m) above the floor. Extinguishers should be mounted in a clean and dry location, accessible 

to possible fire hazards and preferably near an exit. 

Never install the extinguisher in a location where 

a potential hazard would prevent easy access.

     

 

Use the mounting bracket supplied with extinguisher or an approved Victory vehicle bracket if needed. 

Secure to a solid surface using the appropriate fixings for the  surface (not supplied) to firmly hold the 

bracket in place.   

 

The  operational  temperature  range  for  this  extinguisher  is  +40°F  to  +120°F  (+4°C  to  +49°C)  [please 

see  the  nameplate  on  your  extinguisher].    The  extinguisher  should  be  adequately  protected  if 

temperatures outside of this range are anticipated.    Keep the extinguisher clean and free from dirt, ice, 

chemicals,  and  any  contaminants  that  may  interfere  with  its  proper  operation.   

DO  NOT 

FUNCTIONALLY  TEST  THIS  FIRE  EXTINGUISHER

.    (Testing  or  any  use  may  cause  the 

extinguisher to gradually lose pressure over time and make the extinguisher ineffective).    Never throw 

an extinguisher into a fire because rapid heat buildup could cause pressure expansion and exceed the 

limitations of the cylinder.   

 

SERVICE TOOLS 

 

Victory recommend that only  the correct  tools, weighing  scales and pressurizing adaptors  are utilized 

for  service  and  recharge  to  ensure  correct  assembly  and  filling  (See  appendix  B  for  detail).  Victory 

recommended  tightening  torque  values  should  be  followed. 

DO  NOT  OVERTIGHTEN

  or 

CROSS 

THREAD

 any threaded connections.     

 

SAFETY 

 

Victory  recommend  the  appropriate  personal  protective  equipment  (PPE)  is  used  as  described  in  the 

Safety  Data  Sheet  (SDS)  available  on  the  Victory  website.  Observe  instructions  for  disposal  of  any 

agent in accordance with SDS. 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for WM2.5GAL

Page 1: ...at they are ready to operate properly and safely Victory strongly recommends that the maintenance of portable fire extinguishers be done by a trained professional your local authorized Victory Distrib...

Page 2: ...D FAILURE TO HEED THESE INSTRUCTIONS COULD RESULT IN SERIOUS INJURY VICTORY ASSUMES NO LIABILITY FOR SERVICE MAINTENANCE OR RECHARGE OF FIRE EXTINGUISHERS BY PUBLISHING THIS MANUAL REFERENCES IN THIS...

Page 3: ...to 49 C please see the nameplate on your extinguisher The extinguisher should be adequately protected if temperatures outside of this range are anticipated Keep the extinguisher clean and free from d...

Page 4: ...the extinguisher in a vertical position aim the nozzle at the base of the fire 5 Approach fire from upwind minimum of 10 feet of the front edge of the fire 6 Starting back from this distance squeeze t...

Page 5: ...sher connected to a regulator of a high pressure source for an extended period A defective regulator could cause the cylinder to rupture due to excessive pressure CAUTION Discharge time and effective...

Page 6: ...ondition to prevent its operation and any necessary repair or replacement It will normally reveal if hydrostatic testing or internal maintenance is required Maintenance servicing recharging shall be p...

Page 7: ...te the class C capability Do not mix deionized water with non deionized in extinguisher content 6 Visually inspect the pressure gauge a If bent damaged or improper gauge depressurize and replace b If...

Page 8: ...could seriously damage the plastic gauge face 3 Inspect the extinguisher for damaged missing or substitute parts NOTE Only factory replacement parts are approved for use on victory fire extinguishers...

Page 9: ...disassembled valve with a soft bristle brush or soft cloth Blow the valve out with air or nitrogen Inspect the collar O ring valve stem spring and dip tube assembly and replace parts if worn or damage...

Page 10: ...ing facing the front of the extinguisher gauge side 12 Install new tamper seal wrapping through loop and around levers to secure ring pin Do not over stress tamper seal 13 Weigh assembled extinguisher...

Page 11: ...ent De pressurize and replace Install the correct Victory pressure gauge using Teflon tape on the gauge threads 9 Gauge does not indicate compatible with brass De pressurize and replace Install the co...

Page 12: ...will not affect the remainder Victory is not responsible for the installation or the maintenance of the products Defective products for which a valid claim has been made shall be returned to Victory s...

Page 13: ...sociation 2022 Edition 1 Batterymarch Pk P O Box 9101 Quincy MA 02169 7471 www nfpa org CGA C 1 Methods for Hydrostatic Compressed Gas Assoc Inc Testing of Compressed Gas 4221 Walney Road 5th floor Cy...

Page 14: ...14 APPENDIX A...

Page 15: ...ch Pressure Gauge to valve Recommended torque 5 12Nm 44 106 in lbs with sealant glue Scales Filling cylinders with deionized water Recommended accuracy 2 5 or better Pressurizing recharging adaptors S...

Reviews: