background image

I-V9_2

REV_B

I-V9 

/ Style V9 Victaulic

®

 FireLock

 IGS

 Installation-Ready

 Sprinkler Coupling / Installation Instructions

NOTICE

•  Gaskets for the Style V9 are provided with 

Vic-Plus. Additional 

lubrication is not required for the initial installation of wet pipe 
systems that are installed at or continuously operating above 
0°F/–18°C. Refer to Victaulic publication 05.03 for the 

Vic-Plus

 

Safety Data Sheet (SDS), which can be downloaded at victaulic.
com.

Supplemental lubrication is required only if any of the following 
conditions exist. Apply a thin coat of a compatible lubricant to the 
gasket sealing lips, as noted in step 3a on the previous page. It 
is not necessary to remove the gasket from the housings to apply 
additional lubricant to the exterior surface.
•  If the installation or continuous operating temperature is below 

0°F/–18°C

•  If the gasket has been exposed to fluids prior to installation
•  If the surface of the gasket does not have a hazy appearance
•  If the gasket is being installed into a dry pipe system
•  If the system will be subjected to air tests prior to being filled 

with water

•  If the gasket was involved in a previous installation
Lubricated gaskets will not enhance sealing capabilities on 
adverse sprinkler piping conditions. Sprinkler piping condition 
and preparation shall conform to the requirements listed in these 
product installation instructions (refer to step 2 on page 1).

 WARNING

•  Never leave a Style V9 partially assembled. 

ALWAYS TIGHTEN THE HARDWARE 
IMMEDIATELY. A partially-assembled Style 
V9 poses a drop or fall hazard during 
installation and a burst hazard during 
testing.

•  Keep hands away from the opening of the 

Style V9 when attempting to install and 
tighten the Style V9 onto the sprinkler 
piping’s grooved end.

Failure to follow these instructions could 
result in serious personal injury and property 
damage.

4. ASSEMBLE JOINT:

 Assemble the joint by installing the Style V9 onto 

the sprinkler piping's grooved end until contact with the center leg of 
the gasket occurs. Rotate the sprinkler and Style V9 so that the frame 
arms and bolt pads are in alignment with the sprinkler piping, as shown 
above. A visual check is required to verify that the keys of the Style V9 
align with the groove in the sprinkler piping.

 WARNING

•  The bolt shall be tightened until metal-to-metal c ontact occurs 

at the bolt pads.

•  DO NOT continue to tighten the bolt after the visual installation 

guidelines for the Style V9 are achieved.

•  DO NOT attempt to rotate the sprinkler or Style V9 after the bolt 

is tightened completely.

Failure to follow these instructions could cause joint damage or 
improper sprinkler operation, resulting in death or serious personal 
injury and property damage.

Hex Installation Bit Provided 

with Product Shipment

3⁄16-inch

(Bolt End)

¼-inch

(Drive End)

5. TIGHTEN BOLT:

 Using an impact wrench or standard socket wrench 

with the 

3/16

-inch hex installation bit that is provided with the product 

shipment, tighten the bolt until metal-to-metal contact occurs at the bolt 
pads. DO NOT continue to tighten the bolt after metal-to-metal bolt pad 
contact is achieved. Refer to the “Impact Wrench Usage Guidelines” 
section. 

NOTE:

 Do not attempt to rotate the sprinkler or Style V9 after 

the bolt is tightened. If necessary, loosen the bolt before attempting to 
rotate the sprinkler or Style V9, then retighten the bolt as stated earlier 
in this step.

GOOD

BAD

6. Visually inspect the bolt pads at each sprinkler piping connection 
to verify that metal-to-metal contact is achieved in accordance with 
step 5.

Summary of Contents for V9 FireLock IGS

Page 1: ...ortant gasket information 3a If any conditions listed in the NOTICE are met apply a thin coat of a compatible lubricant such as Victaulic Lubricant or silicone lubricant only to the gasket sealing lips CAUTION If any conditions listed in the NOTICE are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to prevent pinching rolling or tearing during installati...

Page 2: ...tempting to install and tighten the Style V9 onto the sprinkler piping s grooved end Failure to follow these instructions could result in serious personal injury and property damage 4 ASSEMBLE JOINT Assemble the joint by installing the Style V9 onto the sprinkler piping s grooved end until contact with the center leg of the gasket occurs Rotate the sprinkler and Style V9 so that the frame arms and...

Page 3: ...assembly Perform trial assemblies with the impact wrench and check the assemblies with a torque wrench to help determine the suitability of the impact wrench Using the same method periodically check assemblies throughout the system installation For safe and proper use of impact wrenches always refer to the impact wrench manufacturer s operating instructions In addition verify that proper impact gr...

Page 4: ...d Feature of Bolt Pad 7 INSTALL BOLT Install the bolt through the housings Verify that the head of the bolt faces the angled feature of the bolt pad as shown above 8 INSTALL NUT Thread the bolt into the nut until the top of the nut is flush with the end of the bolt as shown above Verify that the gasket remains seated in the gasket pocket of the housings and that the nut is engaged with the flat fe...

Reviews: