22. Install the repaired Series 746-LPA Dry Accelerator assembly onto
the nipple above the isolation ball valve.
23. Close
the
¼
-turn vent ball valve of the Series 746-LPA Dry
Accelerator.
24. Open the isolation ball valve of the Series 746-LPA Dry
Accelerator. This will set the accelerator.
25. Observe the system air pressure over a 24-hour period to confirm
system integrity. If there is degradation in system air pressure, find
and correct all leaks.
NOTE:
NFPA requires less than 2-psi/14-kPa
leakage in 24 hours.
26. Notify the authority having jurisdiction that the valve has been
placed back in service.
I-746.LPA_7
Series 746-LPA
INSTRUCTIONS FOR INSTALLING AND REPAIRING SERIES 746-LPA DRY ACCELERATORS
I-746.LPA
INSTALLATION AND REPAIR KIT INSTRUCTIONS