17. Make sure a NEW o-ring is installed on the NEW check valve, as
shown above.
18. Using an adjustable wrench, install the NEW check valve into the
piston, as shown above.
19. Align the bolt holes of the upper and lower housings.
NOTE:
Since
one set of bolt holes is offset, use the marks made in step 4 to aid
in alignment.
20. Insert a cap screw into each of the four holes. Using a
9⁄64
-inch hex
wrench, fully tighten the four cap screws.
21. Re-apply a small amount of pipe joint compound or Teflon* tape
to the nipple above the isolation ball valve. DO NOT get any tape,
compound, or other foreign material into the nipple or openings in
the accelerator.
*TEFLON IS A REGISTERED TRADEMARK OF THE DUPONT COMPANY.
I-746.LPA_6
Series 746-LPA
INSTRUCTIONS FOR INSTALLING AND REPAIRING SERIES 746-LPA DRY ACCELERATORS
I-746.LPA
INSTALLATION AND REPAIR KIT INSTRUCTIONS
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_A