background image

VALVE OPERATION

 WARNING

•  DO NOT actuate or operate the Series 725S Diverter Valve 

with media in the system, or while the valve is pressurized. To 
prevent permanent damage to internal valve components, the 
system must be depressurized, flushed, and free of backfill 
before attempting to index the valve.

Failure to follow these instructions may cause valve damage, 
resulting in serious personal injury and property damage.

DIVERSION SERVICE 

For a directional change of backfill flow to stopes, complete the 
following steps.

1.

  Shut down backfill pump/gravity feed system. 

2.

  Flush piping system with clean water to remove build up on pipes 

and valve.

3.

  Once flushing is complete, rotate the diverter plug from outlet 

“A” to outlet “B”.  (Refer to the “Series 725S Helpful Information” 
table for actuation input requirements. Also, refer to the actuation 
manufacturer’s manual provided with the valve.)

 

Alternatively, follow the method shown in the “Flush Service” 
section of these instructions.  

4.

  At operator’s option, flush the system prior introducing backfill 

to identify and clear flow path blockages as well as providing 
confirmation the backfill will be transported to the desired location.

 CAUTION

•  The Series 725S Diverter Valve should only be used when the 

diverting plug is fully aligned with either outlet port. The valve 
should never be used in a partially open position, or with the 
diverting plug rotated 90 degrees in an attempt to shut off flow.

Failure to follow these instructions will cause premature valve 
wear and leakage, resulting in property damage and voiding any 
Victaulic warranty.

5.

  Resume backfill operation.

FLUSH SERVICE 

When using one outlet for backfill service and one outlet for flush water 
dump to a sump collection area, complete the following steps.

1.

  Shut down backfill pump/gravity feed system. 

2.

  Flush piping system with clean water to remove build up on pipes 

and valve.

3.

  Operate the valve from backfill service direction to the opposing 

port, allowing the flush water to enter a sump collection area.  
(Refer to the “Series 725S Helpful Information” table for actuation 
input requirements. Also, refer to the actuation manufacturer’s 
manual provided with the valve.)   

 CAUTION

•  The Series 725S Diverter Valve should only be used when the 

diverting plug is fully aligned with either outlet port. The valve 
should never be used in a partially open position, or with the 
diverting plug rotated 90 degrees in an attempt to shut off flow.

Failure to follow these instructions will cause premature valve 
wear and leakage, resulting in property damage and voiding any 
Victaulic warranty.

4.

  Once flushing is complete, return valve to backfill service location 

and resume backfill operation.

DUMP SERVICE

To evacuate backfill from the borehole and piping upstream of the valve 
in the event of a system blockage downstream of the valve, complete 
the following steps.  

1.

  Shut down backfill pump/gravity feed system. 

2.

  Operate the valve from the backfill service direction to the 

opposing port, allowing upstream backfill to flow to a safe 
disposal area. (Refer to the “Series 725S Helpful Information” 
table for actuation input requirements. Also, refer to the actuation 
manufacturer’s manual provided with the valve.)

3.

  Flush remaining backfill from the upstream borehole piping with 

clean water to remove build up on pipes and valves.

To recondition the valve for service after a dump event, complete the 
following steps.

4a.

  If rotating the diverter plug back to the backfill blockage side, only 

do so when clean flush water remains in the valve. Do not attempt 
to rotate the diverter back while dry.  After downstream blockage 
is cleared, rotate the diverter plug through several full cycles with 
low pressure water inside the valve to clear any internal debris that 
may have accumulated during the dump event.

 CAUTION

•  After using the Victaulic Series 725S Diverter Valve to dump 

upstream backfill due to a downstream blockage, the diverter 
plug may be rotated back to the original position only with clean 
flush water remaining in the valve.  Rotating the valve while dry 
will result in damage to seals and excessive operating torque. 

Failure to follow these instructions will cause premature valve 
wear and leakage, resulting in property damage and voiding any 
Victaulic warranty.

4b.

  If the backfill has solidified in the downstream piping, the 

diverter valve must be visually inspected to verify that there is no 
solidified backfill in the outlet where the blockage occurred.  This 
will require removal of the coupling at the outlet port where the 
blockage occurred, and may require removal of the entire valve 
from the system. Any debris must be fully removed, and the valve 
must be flushed with water prior to returning the valve to service.

5.

  Resume backfill operation only after the valve has been thoroughly 

cleaned and inspected.

I-725S

INSTALLATION AND OPERATING INSTRUCTIONS

Series 725S Diverter Valve

For complete contact information, visit victaulic.com

I-725S     11665 REV B      UPDATED 05/2019       Z000725S00

VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY AND/OR ITS AFFILIATED ENTITIES IN THE UNITED STATES AND/OR OTHER COUNTRIES.                                
© 2019 VICTAULIC COMPANY.       ALL RIGHTS RESERVED.

Summary of Contents for 725S Series

Page 1: ...d and drained immediately prior to installation removal adjustment or maintenance of any Victaulic products Wear safety glasses hardhat foot protection and hearing protection Failure to follow these instructions could result in death or serious personal injury and property damage I 725S REV_B I 725S INSTALLATION AND OPERATING INSTRUCTIONS Series 725S Diverter Valve ...

Page 2: ...Ring 10 Backup Ring 11 Lower Shaft Bearing 12 Body Seal 13 Body 14 Thrust Bearing 15 Adjusting Nut 16 Counter Nut 17 Hex Socket Head Cap Screw 18 Hex Nut 19 Set Screw 20 Top Seal 21 Backup Ring 22 O Ring ASSEMBLY OF THE HANDWHEEL Gear Input Shaft Key Circlip Handwheel 1 Place the key onto the gear input shaft 2 Install the handwheel over the gear input shaft 3 Attach circlip in front of the handwh...

Page 3: ...ny other external loads Using both lifting lugs support the valve to ensure balanced loading In addition a cradle or cribbing can be used to provide increased support WELDING TO SERIES 725S DIVERTER VALVES AND COUPLINGS IS NOT PERMITTED ACTUATOR SETUP Always refer to the actuator manufacturer s manual for complete setup and operating requirements Actuators are designed to operate within the parame...

Page 4: ...use premature valve wear and leakage resulting in property damage and voiding any Victaulic warranty 4 Once flushing is complete return valve to backfill service location and resume backfill operation DUMP SERVICE To evacuate backfill from the borehole and piping upstream of the valve in the event of a system blockage downstream of the valve complete the following steps 1 Shut down backfill pump g...

Reviews: