I-725S 

/ Series 725S Diverter Valve

 

/ Installation and Operating Instructions

NOTICE

•  Drawings and/or pictures in this manual may be exaggerated for clarity.
•  The product, along with these installation and maintenance instructions, contains trademarks, copyrights, and/or patented features that are 

the exclusive property of Victaulic.

Operator

ISO 5211 

Mounting 

Flange

Lifting 

Lug

Lifting 

Lug

INSTALLATION INFORMATION

Series 725S Diverter Valves are available with three different types of 
pipe preparation, for use with three types of Victaulic products.

• 

Cut grooved pipe ends, for use with Victaulic EndSeal™ couplings

• 

Double grooved pipe ends, for use with Victaulic Style 808 couplings

• 

Pipe prepared with rings, for use with Victaulic Style 809 couplings

Series 725S Diverter Valves can be installed in horizontal or vertical 
positions, or in any intermediate position that allows for access to the 
actuator or gear operator.
Series 725S Diverter Valves and connecting  piping must be supported 
to prevent the joints from being  subjected to bending loads, shear loads, 
or any other external loads.

• 

Using both lifting lugs, support the valve to ensure balanced 
loading. In addition, a cradle or cribbing can be used to provide 
increased support.

• 

WELDING TO SERIES 725S DIVERTER VALVES AND 
COUPLINGS IS NOT PERMITTED.

ACTUATOR SETUP

Always refer to the actuator manufacturer’s manual for complete setup 
and operating requirements.
Actuators are designed to operate within the parameters specified in 
the table below. Additional information will be required to determine 
appropriate specifications for your system.

SERIES 725S HELPFUL INFORMATION

Operator/Actuator Performance

Size

Manual (Gear Operator)

Pneumatic

Hydraulic

Electric 

Nominal

inches

 

DN

Number of  

Turns from  

Flow Position A  

to  

Flow Position B

Hand Wheel 

Dimensions

inches 

mm

Rim Pull 

lbf 

N

Supply Air

RPM

 

Supply Fluid

RPM

 

RPM

 

Pressure

psi 

bar

Flow  

Rate

SFPM 

l/s

Pressure

psi 

bar

Flow  

Rate

gpm 

l/s

4

80

24.80

51

92

32

109

2500

30

2000

90

DN100

630

69

6.3

15

172

1.84

6

80

24.80

67

92

42

100

2500

30

2000

90

DN150

630

91

6.3

20

172

1.84

8

109

24.80

77

92

85

90 

§

2500

30

2000

90

DN200

630

104

6.3

40 *

172

1.84

NOTE: For additional actuation requirements, contact Victaulic.
* for Australia only: 61 l/s

§ 

for Australia only: 192 RPM

 electrical requirements vary based on voltage

I-725S_3

REV_B

Summary of Contents for 725S Series

Page 1: ...d and drained immediately prior to installation removal adjustment or maintenance of any Victaulic products Wear safety glasses hardhat foot protection and hearing protection Failure to follow these instructions could result in death or serious personal injury and property damage I 725S REV_B I 725S INSTALLATION AND OPERATING INSTRUCTIONS Series 725S Diverter Valve ...

Page 2: ...Ring 10 Backup Ring 11 Lower Shaft Bearing 12 Body Seal 13 Body 14 Thrust Bearing 15 Adjusting Nut 16 Counter Nut 17 Hex Socket Head Cap Screw 18 Hex Nut 19 Set Screw 20 Top Seal 21 Backup Ring 22 O Ring ASSEMBLY OF THE HANDWHEEL Gear Input Shaft Key Circlip Handwheel 1 Place the key onto the gear input shaft 2 Install the handwheel over the gear input shaft 3 Attach circlip in front of the handwh...

Page 3: ...ny other external loads Using both lifting lugs support the valve to ensure balanced loading In addition a cradle or cribbing can be used to provide increased support WELDING TO SERIES 725S DIVERTER VALVES AND COUPLINGS IS NOT PERMITTED ACTUATOR SETUP Always refer to the actuator manufacturer s manual for complete setup and operating requirements Actuators are designed to operate within the parame...

Page 4: ...use premature valve wear and leakage resulting in property damage and voiding any Victaulic warranty 4 Once flushing is complete return valve to backfill service location and resume backfill operation DUMP SERVICE To evacuate backfill from the borehole and piping upstream of the valve in the event of a system blockage downstream of the valve complete the following steps 1 Shut down backfill pump g...

Reviews: