2
| 028-0363-03
November 2015
Fig. 1
I
nstallatIon
Remove security screw on bottom of Room
Controller cover.
•
Open unit by pulling on bottom side
of Room Controller (Fig. 1).
•
Remove wiring terminals from sticker.
•
Read the FCC ID and IC label in-
stalled in the cover.
Location
1. Should not be installed on outside
wall.
2. Must be installed away from any
direct heat source.
3. Should not be installed near an air
discharge grill.
4. Should not be affected by direct sun
radiation.
5. Nothing should restrict vertical air
circulation to the Room Controller.
Installation
1. Swing open Room Controller PCB
to left by pressing PCB locking tabs
(Fig. 2).
2. Pull out cables 6” out from wall. En-
sure wall surface must is and clean.
3. Insert cable in central hole of base.
4. Align base and mark location of two
mounting holes on wall ensuring
proper side of base is up.
5. Install anchors in wall.
6. Insert screws in mounting holes on
each side of base (Fig. 2).
7. Gently swing back circuit board on
base and push until tabs lock.
8. Strip each wire 1/4 inch from end.
9. Insert each wire according to wiring
diagram.
10. Gently push excess wiring back into hole (Fig. 3).
11. Re-Install wiring terminals in their correct locations (Fig. 3).
Location of PCB retaining tabs
Fig. 2
Re-install terminal blocks
Fig. 3