SLAVE APPLICATION SECTION
When using a unit for slave applications, it is important that the proper adjustments & setting be made to the unit for proper
operation of the system.
The yellow LED near the vernier output connector is proportional to the vernier output of the master unit ( 0 to 5 Vdc ).
On the slave unit:
•
Set vernier ratio potentiometer to 100%
•
Set interstage delay potentiometer to the same value as the master unit
ON
•
Set all control signal
INPUT
dip switch to
OFF
TEST MODE BUTTON
The test mode button can be used to verify if the number of stage have been configured properly.
1. Press and hold the button for 3 to 4 seconds.
2. If a slave unit is used, press & hold the 2 units button simultaneously
3. All the selected stage will come on, one after the other until all selected number of stages are all on.
4. There is a delay of approximately 5 second between each step activation.
5. When all selected stage are on, they will stay on for approximately 30 seconds before shutting down.
Powering up the R851V controller while holding down the test button will by-pass the interstage delay for 10 minutes. During
that period, the unit will respond to a changing signal input very rapidly. Also hold down slave test button on start-up if a
slave unit is used. After that 10 minute period, the unit will function normally with the interstage delays active
CALIFORNIA PROPOSITION 65
WARNING
CALIFORNIA PROPOSITION 65
This product can expose you to chemicals including Lead, which are known to the State of California to cause cancer and birth
defects or other reproductive harm. For more information, go to
Failure to follow these instructions can result in birth defects or other reproductive harm.
Viconics Technologies Inc.
7262 Marconi | Montreal | Quebec | Canada | H2R 2Z5
Tel.
: 514.313.8885 | Toll free: 1 800.563.5660
4
1 2
1
2
3
I N P U T