Viatran DL Series Analog Input Process Meter Instruction Manual
29
Display Parameter
Action/Setting
Description
d-Inty
Display
intensity
Set display intensity level from 1 to 8
RELaY
Relay
Enter the
Relay
menu
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for automatic reset
A-nman
Auto-manual
Set relay for automatic & manual reset any
time
LatCH
Latching
Set relay for latching operation
Lt-CLr
Latching-
cleared
Set relay for latching operation with
manual reset only after alarm condition
has cleared
Altern
Alternate
Set relay for pump alternation control
Sanmpl
Sampling
Set relay for sampling operation
OFF
Off
Disable relay and front panel status LED
(Select Off to enable Interlock feature)
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-8 setup
Note: Relays 5-8 are shown, only if
expansion relay module is installed.
FaiLSF
Fail-safe
Enter
Fail-safe
menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe operation
on
On
Enable fail-safe operation
off
Off
Disable fail-safe operation
FLS 2
Fail-safe 2
Set relays 2-8 fail-safe operation
DeLAY
Delay
Enter relay
Time Delay
menu
DLY 1
Delay 1
Enter relay 1 time delay setup
On 1
On 1
Set relay 1 On time delay
OFF 1
Off 1
Set relay 1 Off time delay
DLY 2
Delay 2
Enter relays 2-8 time delay setup
break
Loop break
Set relay condition if loop break detected