16
371101.11
Installation manual E-Air electric propulsion
6.5 Main current cables
• Connect the motor to the batteries as shown in the diagrams, see
.
• Fit the fuse supplied and a main switch in the positive (+) cable.
W
arninG
When calculating the cable cross-sections, take into account a
maximum permissible voltage drop of 5%.
Never use smaller cable cross-sections than indicated in the
table below.
Motor type
EAIR040
Maximum input power
5,5 kW
Battery cable
70 mm
2
Fuse
250 A
When the batteries are not being used or not charged, it is recom-
mended that they are disconnected from each other using an isolat-
ing switch.
W
arninG
NEVER fit the fuse, main switch or isolating switches in the
battery space!
Take the following points into account when installing the battery
cables:
- Fit the cables in the shortest possible way from batteries to motor.
- With a long cable length, bundle the ‘+’ and ‘-’ cables together.
- Install the ‘+’ and ‘-’ preferably in such a way that the total length of
each cable is the same. This ensures an equal load on each battery.
- Ensure that the cables do not run through any bilge water.
- Ensure that the cables cannot come into contact with any sharp
edges.
- Fix the cables in such a way to prevent wear or abrasion caused
by vibration.
- Use cable terminals to connect the cables to switches, fuse and
motor.
- Preferably fit cable terminals by crimping.
- Use good quality battery terminals to connect the cables to the
battery posts.
- Tighten bolts securely to ensure a good connection.
- Do not use spring-loaded battery terminals!
- Grease the battery posts and battery terminals with Vaseline to
prevent corrosion.
- Never change over the connector cables.
- Before leaving, check the charge status of the batteries just as you
would check the tank capacity of a diesel engine.
W
arninG
Changing over the plus (+) and minus (-) connections will
cause irreparable damage to the installation.
W
arninG
NEVER short-circuit the batteries by connecting the plus (+)
pole to the minus (-) pole.
Connecting the main current cables
• Switch all electrical equipment off.
• Prevent any short circuits caused by tools, for example.
• Connect the positive (+) cable first, then the negative.
Power consumption indication displacement vessel
Waterline length
4 m (13 ft)
6 m (19 ft)
8 m (26 ft)
10 m (33 ft)
Gentle sailing
6 km/h (3.3 kn)
6 km/h (3.3 kn)
6 km/h (3.3 kn)
6 km/h (3.3 kn)
1 kW
0.7 kW
0.8 kW
1 kW
Cruising speed
7.2 km/h (3.8 kn)
8.8 km/h (4.7 kn)
10.2 km/h (5.5 kn)
11.4 km/h (6.1 kn)
1.5 kW
2.1 kW
3.9 kW
6.7 kW
Hull speed
9 km/h (4.9 kn)
11 km/h (5.9 kn)
12.8 km/h (6.9 kn)
14.3 km/h (7.7 kn)
3.1 kW
4.1 kW
7.7 kW
13.4 kW