IF SMI KNX 24VDC

Subject to modifications.

ETS communication objects

ETS parameters

“Drive error status” object

Use this object to read out a potential drive error. The actuator transmits
the status spontaneously when the general parameter “Send status
objects” is set to “For status change”.

Object value “0”: no error
Object value “1”: error present

8/ 15

G

“Save scene pos 1/pos 2, channel x” object (manual mode)

Use this object to store the existing position of shade height and slat angle
(for blinds) in the actuator under pos1 or pos2. Storage however only takes
place if the drive is standing at the time the telegram is input.

Object value “0”: store pos1
Object value “1”: store pos 2

NOTE!

Whenever sensible, the actuator software tries to execute simultaneously incoming travel commands (e.g. “Stop/Step travel, channel x”) of
several channels (if they are entered with the same group address for instance) also with corresponding SMI group commands for the chan-
nels concerned. This ensures the connected drives operate synchronously where possible. In the case of Step commands, the drives are also
grouped in accordance with the same value of the step length parameter.

i

(Parameter presets are in bold)

Parameter

Setting

Description

Dependent on

Transmit status objects

only for
reading request

for status change

Use this parameter to set whether the “position” and “drive error”
status objects of all channels can only be read out or whether
after reaching a new shade height or slat angle position or upon
occurrence or discontinuation of a drive error the corresponding
value should automatically be transmitted.

During bus voltage
recovery

send nothing

send status objects

Use this parameter to set whether, once bus voltage has been
recovered, the “position” and “drive error” status objects of all
channels should be transmitted.
Transmission occurs, if appropriate, after a time delay which is
dependent on the physical address of the actuator, thus avoiding
bus conflicts caused by too many actuators transmitting at the
same time.

Send status objects =
“For status change”

Safety

without time monitoring

with time monitoring

This parameter is used to set whether the cyclical reception
of telegrams will be monitored over time in conjunction with
the safety object.

Monitoring time
for safety

1 minute
5 minutes

10 minutes

30 minutes

If the “Safety” parameter is set to “with time monitoring”,
this parameter can be used to set the maximum permitted time
between telegrams with a logical zero with regard to the safety
object.

Safety = 
“with time monitoring”

Parametrisation
of drives

individual

all equal

This parameter allows you to determine whether the channels
or drives should be parametrised individually or be made iden-
tical. In the case of individual parametrisation, a corresponding
parametrisation tab will appear for each channel that is selected
as “used”. If the “all equal” setting is used, these tabs and
parameters will only appear once and these will then determine
the behaviour of all channels together.

Addressing mode

automatic

per manufacturer and
SMI key ID

In the case of automatic addressing, the actuator independently
programs all configurable drives (those with slave address 0)
with the slave addresses designated in accordance with the
ETS. The highest SMI slave address is thus assigned to the
highest SMI key ID.
If addressing is set to occur per manufacturer and SMI key ID,
the actuator attributes the slave addresses according to the
assignment from the ETS parametrisation.

Re-addressing

automatic

enforce

This parameter can be used to trigger a re-programming of the
slave addresses (that have been parametrised according to the
ETS) in the drives.

“General” tab

Summary of Contents for IF SMI KNX 24VDC

Page 1: ...ter unpacking If you notice any shipping damage do not start up the control system and notify your supplier immediately The control system should only be used for the purpose speci fied by the manufac...

Page 2: ...lso be carried out via the EIB see following section In addition to ETS parametrisation a UIO user interface object interface can be used in order to obtain access to the internal actuator SMI con fig...

Page 3: ...y This state has the second highest priority If a safety object with a 1 value occurs the state of the actuator changes into Safety mode in the event of existing travel command lock of the masked stat...

Page 4: ...d shade slat position 5 Bring current movement to end 1 3 Move to safety position 1 1 0 0 Up and down 0 Step up and down 0 Move to scene 1 Save scene 1 Movement to and storage of setpoint position 1 M...

Page 5: ...settings the appearance of the respective element is dependent on Special reference is however no longer made in detail to the basic depen dency that channel specific objects only appear for activated...

Page 6: ...bit value 8 bit KL send 10 Move to scene pos1 pos2 channel 1 Manual mode Pos1 Pos 2 1 bit AKS receive 11 Save scene pos1 pos2 channel 1 Manual mode Pos1 Pos 2 1 bit AKS receive 12 Drive error status c...

Page 7: ...ating mode can also be carried out by other objects using the priority circuit of the operating modes For this see state administration and state table This object is only visible if automatic mode is...

Page 8: ...to set whether once bus voltage has been recovered the position and drive error status objects of all channels should be transmitted Transmission occurs if appropriate after a time delay which is depe...

Page 9: ...eter and use of drive 1 used Manufacturer code of drive 2 any Alcatel Becker Elero Selve 5 Vestamatic Varema 8 9 15 If per manufacturer and SMI key ID addressing is chosen the drive manufacturer can b...

Page 10: ...ed If the Locked setting is selected the objects Position of sunshade and Position of slat angle will be interpreted as manual mode objects Behaviour during bus voltage failure no action travel upward...

Page 11: ...vel command lock is active for the particular channel If the lock is released and switched on all incoming travel commands via the EIB will be blocked Behaviour during bus voltage failure no action tr...

Page 12: ...n of the drives if necessary Initialisation using drives with non programmed slave addresses or slave address 0 If during initialisation no drives answer at one or more addresses preset in accordance...

Page 13: ...d warnings are stored each in a property in the device object of the actuator Property 201 hex C9 contains the warnings Property 202 hex CA con tains the errors The corresponding table of errors and w...

Page 14: ...for initialisation are also immediately acknowledged by the actuator in the control byte Due to continuous read out of the byte it is therefore possible to determine the processing status of the parti...

Page 15: ...alised in a clear assignment to the drive IDs Work with the gateway property 64 is then made considerably easier Any commands can be entered as hex strings and the processing and respon se status is t...