background image

© Vestamatic GmbH

Ar

t.-Nr

.:

84501110 E1  •  

V

estamatic GmbH  •  Dohrw

eg 27  •  D-41066 Mönchengladbach  •  www

.v

estamatic.com

IF SMI KNX 24VDC

Subject to modifications.

Planning and activation

In the same way, the properties in the user interface object 50001 can be
checked and interpreted using the description outlined further below.
Please refer to “User interface object 50001 and properties therein”. The
SMI Tool is a diagnostic aid with very wide-ranging possibilities. It will
make access to individual actuators and the corresponding properties of
the user interface object 50001 much easier (see the following).

The user interface objects and properties have an interface which enables
(via the EIB through use of appropriate tools) further diagnoses, settings
and interventions, particularly on the SMI side at the particular actuator.
The use of the UIO interface is possible either via a standard tool such as
the Device Editor from the ETS3 accessories, or via a special tool that can
be used independently of the ETS but is used for the communication with
the particular actuator from the Falcon library and the EIB. The free soft-
ware assumes that the Falcon library (an integral component of, for exam-
ple, ETS3) is available.
However, the use of the UIO interface with, for instance, the Device Editor
requires the user to have special knowledge and a certain degree of ex-
perience. This chapter should therefore be read thoroughly and under-
stood. It is recommended that use with the Device Editor is reserved only
for emergencies, for instance for the diagnosis of otherwise inexplicable
faults. It is much simpler to use the UIO interface with the SMI tool (see
“The SMI software”).
The actuator software supports, in addition to the interface objects set out
in the EIB standard, another object with the ID “50001”, which supports
diagnosis and provides certain setter functionality for the actuator-con-
nected SMI bus and its devices. The above-mentioned software visualises
the properties provided via the user interface object 50001, thus enabling
a clear diagnosis. The software provides a practical way of intervening in
the SMI addressing of slave drives and in their parametrisation.
Essentially it is also possible to access the SMI drives directly and to
transmit any conceivable SMI command to the individual connected slaves
through the particular actuator acting as an SMI gateway. This is where
property 64 is used. As access is provided via the EIB, no hardware con-
nection to the particular SMI bus is required. Communication is conveyed,
via the physical address of the actuator concerned in the EIB, to the
appropriate SMI bus. Of course, drives may also be parametrised physi-
cally.

Errors and warnings in properties 201 & 202 in the device object

The actuator’s EIB operating system “System 2” provides further proper-
ties (in addition to those specified in the KNX standard) in the device
object that are partially co-used by the actuator’s application firmware.
In particular, the properties 201 and 202 in the device object allow
access to errors and warnings, thus supporting a diagnosis in the event of
faults.

Also written in these properties by the operating system are, if appropriate,
warnings or errors. The latter have codes 

k

hex 6F and are described in

the documentation on System 2; those of the application of the actuators
have codes 

g

hex 70 and are summarised in the following table.

Errors and warnings during initialisation

Irrespective of the mode of addressing, the actuator will generate corre-
sponding error codes if an assignment attempt is unsuccessful. Warning
codes are generated if, for instance, slaves are reprogrammed or it is iden-
tified that slaves have been exchanged. The 6 last different errors and
warnings are stored each in a property in the device object of the actuator.
Property 201 (hex C9) contains the warnings; Property 202 (hex CA) con-
tains the errors. The corresponding table of errors and warnings in proper-
ties 201 & 202 in the device object displays the possible error and warning
codes and their causes.

Procedure for planning and activation

The basic addressing modes of “automatic” and “per manufacturer and
SMI key ID” should be selected according to whether the drive data
(manufacturer and key ID) of the drives can be or has been recorded by
the installer during installation.

Many manufacturers help here by supplying the drives, the shades or the
cable with peelable stickers detailing the drive’s key ID. If the drive data is
clearly assigned to the drives’ installation locations, the setter can usually
carry out the activation through “per manufacturer and SMI key ID” addres-
sing with a single ETS download per actuator. This process also has the
advantage that all drive data is then documented in the ETS project.

In all other circumstances, “automatic” addressing should be used, which
may require appraisal of the initial random assignment after the first down-
load. After the slave addresses have been re-sorted in the ETS and follow-
ing a new download, the assignment is complete.
Even if the drives have been programmed with known slave addresses,
these can be entered straight into the ETS. If the spatial distribution of the
drives with these addresses is known from the outset, the assignment via
the channels can be set with similar precision. If the position of the drives
is not known, this can be determined after the initial ETS download
through operation via the EIB and then re-sorted.
If preprogrammed drives or partly pre-programmed, partly non-prepro-
grammed drives are used with unknown slave addresses, the actuator can
be initiated with the re-addressing = “enforce” parameter in order to pre-
program all slaves with the slave address 0. Thereupon the actuator will
program all connected slaves, according to the selected mode of addres-
sing, with the slave addresses given in the ETS. Whether the channel
assignment is then complete depends on the addressing procedure (see
above).

Options in the case of errors during planning and activation

If, during a full re-addressing process, more key IDs (i.e. slaves) have been
found than there are slave addresses available according to the ETS para-
metrisation, the remaining drives (key IDs) keep the slave address 0.
Alternatively, if fewer key IDs are found than there are slave addresses
available according to the ETS parametrisation, no drives will be assigned
to the remaining slave addresses or channels – the channels remain
without function.

Other possible errors during activation may be identified, whereby the pro-
perties 201 and 202 are read out from the device object (if appropriate
with the Device Editor from the ETS 3 accessories).

13/15

G

Code

Type

Description

Cause

0x73

Error

SMI transmission time-out

Error in SMI communication during transmission, possibly no SMI power.

0x74

Error

EEPROM error

Data error in EEPROM (checksum faulty), ETS download may be faulty.

0x76

Error

Slave programming error

An attempt to program a slave has failed.

0x77

Error

Slave address duplicated

A slave address has been assigned twice (same for two channels) in the ETS.

0x78

Warning

Unknown slave

A slave has been found that is not present in the ETS parametrisation.

0x7a

Warning

EEPROM updated

One or more new or exchanged slaves have been identified.

0x7b

Warning

Enforced new programming

All slaves are re-programmed according to ETS parameters.

0x7c

Warning

Missing slaves

It has not been possible to assign all the slaves that, according to the ETS, should be available.

0x7d

Warning

Incorrect key ID ignored

A slave is ignored because it has a different key ID to the one expected according to the ETS.

User interface objects and properties (UIO interface)

Summary of Contents for IF SMI KNX 24VDC

Page 1: ...ter unpacking If you notice any shipping damage do not start up the control system and notify your supplier immediately The control system should only be used for the purpose speci fied by the manufac...

Page 2: ...lso be carried out via the EIB see following section In addition to ETS parametrisation a UIO user interface object interface can be used in order to obtain access to the internal actuator SMI con fig...

Page 3: ...y This state has the second highest priority If a safety object with a 1 value occurs the state of the actuator changes into Safety mode in the event of existing travel command lock of the masked stat...

Page 4: ...d shade slat position 5 Bring current movement to end 1 3 Move to safety position 1 1 0 0 Up and down 0 Step up and down 0 Move to scene 1 Save scene 1 Movement to and storage of setpoint position 1 M...

Page 5: ...settings the appearance of the respective element is dependent on Special reference is however no longer made in detail to the basic depen dency that channel specific objects only appear for activated...

Page 6: ...bit value 8 bit KL send 10 Move to scene pos1 pos2 channel 1 Manual mode Pos1 Pos 2 1 bit AKS receive 11 Save scene pos1 pos2 channel 1 Manual mode Pos1 Pos 2 1 bit AKS receive 12 Drive error status c...

Page 7: ...ating mode can also be carried out by other objects using the priority circuit of the operating modes For this see state administration and state table This object is only visible if automatic mode is...

Page 8: ...to set whether once bus voltage has been recovered the position and drive error status objects of all channels should be transmitted Transmission occurs if appropriate after a time delay which is depe...

Page 9: ...eter and use of drive 1 used Manufacturer code of drive 2 any Alcatel Becker Elero Selve 5 Vestamatic Varema 8 9 15 If per manufacturer and SMI key ID addressing is chosen the drive manufacturer can b...

Page 10: ...ed If the Locked setting is selected the objects Position of sunshade and Position of slat angle will be interpreted as manual mode objects Behaviour during bus voltage failure no action travel upward...

Page 11: ...vel command lock is active for the particular channel If the lock is released and switched on all incoming travel commands via the EIB will be blocked Behaviour during bus voltage failure no action tr...

Page 12: ...n of the drives if necessary Initialisation using drives with non programmed slave addresses or slave address 0 If during initialisation no drives answer at one or more addresses preset in accordance...

Page 13: ...d warnings are stored each in a property in the device object of the actuator Property 201 hex C9 contains the warnings Property 202 hex CA con tains the errors The corresponding table of errors and w...

Page 14: ...for initialisation are also immediately acknowledged by the actuator in the control byte Due to continuous read out of the byte it is therefore possible to determine the processing status of the parti...

Page 15: ...alised in a clear assignment to the drive IDs Work with the gateway property 64 is then made considerably easier Any commands can be entered as hex strings and the processing and respon se status is t...

Reviews: