39
Caution:
Care must be taken not to damage the cable running to the manifold.
Attention :
Faites attention de ne pas endommager le câble qui arrive au distributeur.
Note:
The chassis consists of the Detection Chamber, head processor card and flow sensors. These are
factory calibrated as a matched set and must not be separated. Separating the set and replacing it
with components from another VESDA VLP will cause the detector to malfunction. This will require
the chassis to be returned to the factory.
8. Disconnect the flow sensor lead.
9. Unscrew manifold retaining screws.
Figure 11-4: Removing pipe inlet manifold
10. Remove the manifold by sliding it downward, away from the pipe network.
11. Attach the replacement manifold and chassis by reversing the procedure above.
12. Configure the node using Xtralis VSC by highlighting the detector in the Device Tree window and
highlighting ‘Restore Node Configuration’ from the Device menu, or reprogram the detector using the
LCD Programmer.
Note:
Data cables must be plugged and unplugged only after power has been removed. Ensure all
connectors are seated correctly before applying power to unit. Failure to observe this requirement
may cause data corruption that requires factory recalibration.