27
6.1.3
Typical Wiring To Fire Alarm Control Panel (FACP)
The diagram below shows the correct way to wire VESDA laser detectors to a conventional fire alarm control
panel (FACP). It also shows where an End Of Line (EOL) resistor is correctly installed.
Normally Closed (NC)
Common
FIRE 1
(C)
(NO)
Normally Open
Normally Closed (NC)
Common (C)
ACTION
(NO)
Normally Open
Normally Closed (NC)
Common (C)
FAULT
(NO)
Normally Open
GPI
(
)
Set to reset
Dete tor
c
(NC)
(C)
Reset
(NO)
Input
Short = Fire
Open = Fault
To next detector
or End of Line resistor (EOL)
Fire Panel (FACP)
+
-
5-30VDC
+
-
The relay is
energised
on reset.
Figure 6-5: Typical wiring to a fire panel with EOL
6.1.4
Wiring To an Addressable Loop Module
This wiring example is for wiring VESDA detectors to a typical Addressable Loop module 3 input 1 output.
These are example drawings. Refer to the appropriate product manual for the exact wiring details of the third
party equipment.
Normally Closed (NC)
Common (C)
FIRE 1
(NO)
Normally Open
Normally Closed (NC)
Common (C)
ACTION
(NO)
Normally Open
Normally Closed (NC)
Common (C)
FAULT
(NO)
Normally Open
GPI
“R
”)
(Set to
eset
Dete tor
c
(NC)
(C)
Reset
(NO)
Fire Input
EOL* = Normal
Short = Fire
Open = Wiring Fault
3
1
Inputs
Output Loop Module
To FACP
To Next Detector
Pre Alarm
EOL* = Normal
Short = Fire
Open = Wiring Fault
Fault Input
EOL* = Normal
Short = Detector Fault
Open = Wiring Fault
EOL*
EOL*
EOL*
*EOL: End of Line Resistor
The relay is
energised
on reset.
Relay shown energized which
is the no-fault condition
+
-
5-30VDC
+
-
Figure 6-6: Addressable Loop Module with EOL