VESDA-E VEP-A10-P Product Guide
38
www.xtralis.com
Notes:
l
The polarity of the data wires must be maintained throughout the network.
l
In order for the detector to be able to detect ground faults on the VESDAnet wiring, the Ground Reference
Terminal (Figure 4-33) must be connected to the local ground.
A+
A-
B-
Shield
Module 1
Module 2
Module 3
Module 5
Module 4
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
(VESDA-E VEP)
Figure 4-35: Example closed loop VESDAnet network
The VESDA-E VEP-A10-P detector is shipped with the VESDAnet A and B terminals looped. Remove the A
and B links prior to connecting the detector to the VESDAnet. If the detector is not to be networked with other
devices, then do not remove the A and B links.
Shield
A-
A+
Shield
B-
B+
Figure 4-36: Closed loop for standalone detectors with VESDAnet capability
Note:
Refer to the VESDA-E Communications Guide for further information.
Summary of Contents for VEP-A10-P
Page 2: ......
Page 10: ...VESDA E VEP A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 22: ...VESDA E VEP A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...
Page 54: ...VESDA E VEP A10 P Product Guide 48 www xtralis com This page is intentionally left blank ...
Page 82: ...VESDA E VEP A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEP A10 P Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 110: ...VESDA E VEP A10 P Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 116: ...VESDA E VEP A10 P Product Guide 110 www xtralis com Z zone 59 61 79 105 ...