VESDA
®
LaserCOMPACT Product Manual
Version 1.0
19
Parameter
Default Value
Minimum
Access Level
Overlay Alert
Not Selected
Adm
Power Supply Zone Number
0
Adm
Reference Detector…Delay
2 minutes
Adm
Reference Detector…Detector
255 = No Reference
Adm
Reference Detector…Dilution
100%
Adm
Smoke Change…Change By
0.02% obs/m (0.0062% obs/ft)
Adm
Smoke Change…Min Interval
2 seconds
Dst
UL Flag restricting maximum Threshold
Set
Adm
Units
SI
Adm
Zone Name/Location
Blank
Adm
Zone Number
0
Adm
7. Alarm Threshold Settings
Alarm Threshold
Settings (Default)
UL Alarm Threshold
Settings
% obs/m
% obs/ft
% obs/m
% obs/ft
Alert (min)
0.005
0.0015
0.005
0.0015
Alert (max)
1.990
0.6218
1.990
0.6218
Pre-Alarm (min)
0.010
0.0031
0.010
0.0031
Pre-Alarm (max)
1.995
0.6234
1.995
0.6234
Fire (min)
0.015
0.0046
0.015
0.0046
Fire (max)
20.0
6.25
12.8
4.0
UL Specs:
To meet UL specifications, Any alarm thresholds (signal) that initiates an
evacuation procedure via the Fire Alarm Panel must not be set higher than
0.625%/ft.