background image

Action

Operation

Emergency power-off.

Press the EPO button on the front door of the Control Panel and
Fire Suppression System.

Press the Remote EPO (REPO) button(s) if they are connected
to the system.

Note: Systems manufactured and shipped after August 26,
2016, have the latching EPO button.

The EPO button is a latching button.

To engage the EPO: Press the button until it latches and the system shuts down.

To disengage the EPO: Pull-out the EPO button.

When engaged, all cooling units, UPS(s) (if wired into EPO circuit), Fire suppression
and emergency ventilation fans (if running) power down. There are multiple ways to
configure the EPO circuit per the electrical schematic to comply with local codes, so
your operation may vary. However, all equipment can be wired to shut down.

If equipped, the Shunt trip breaker in the load panel can be wired to open as well.

Resetting emergency ventilation fans.

Push the High Temp Reset button after an event in which the
fans have activated and lowered the return air temperature to
89°F ±3°F or lower

Deactivates the emergency ventilation fans after the safe temperature is reached.

Allows cooling unit to reactivate when possible (Utility power restored, alarm cleared,
etc.).

Resets the control logic for the Emergency Ventilation Fans for future activation.

Note: Do not reset emergency ventilation fans for at least 2 minutes after they
activate to ensure that the thermal unit’s 2 minute restart delay has expired.

Turning the fire-suppression control bypass timer.

Turn the timer past the 1-hour position

Suspend the fire-detection so that maintenance can be performed on the system.

The timer provides a normally-closed circuit bypassing the internal, normally closed
relays in the fire-suppression panel.

Once the timer expires, the circuit is returned to its normal setting (Off).

Note: You can turn the timer up to a maximum of two hours if necessary to perform
maintenance.

To continue the bypass operation, just turn the timer again when time gets low.

Turning the Vertiv™ SmartRow™ DCX emergency power-off
override timer.

Turn the timer past the 1-hour position.

Temporarily bypass the EPO circuit. This allows manual restart of the UPS after an
EPO event.

Note: You can turn the timer up to a maximum of two hours if necessary to perform
maintenance.

To continue the bypass operation, just turn the timer again when time gets low.

Turning the key to activate the manual fire-suppression
release.

If you see smoke and/or fire in the system, but the smoke detector is malfunctioning,
you can manually discharge the fire suppression material into the system.

Fire-suppression system abort

Prevents the fire-suppression system from dumping due to a false alarm.

Control Power Available light illuminated (green)

Control system is powered via TB1 positions (1 & 2) or (3 & 4).

Control Power Available light is NOT illuminated

Green LED indicates all doors are closed.

Main Circuit Breaker with Shunt Trip Assembly (If applicable)

To enable power flow to the control panel, flip
the breaker switch to the UP position
(On/Closed).

To disable power flow to the control panel, flip
the breaker switch to the DOWN position
(Off/Open)

Eliminates power to all loads connected to and downstream of the load distribution
center both locally and remotely.

IMPORTANT! The shunt trip assembly requires a dedicated, field-supplied source of 120V
power to TB1 Pins 9 & 10.

If the breaker is tripped (EPO activation), you must reset the breaker before beginning
the restart protocols. See

Recovering from a Fire Suppression System Activation

on

the next page, for details.

Table 6.1 Component operation for the Vertiv™ SmartRow™ DCX Control Panel and Fire Suppression System

Vertiv

| SmartRow™ DCX Installation Manual |

23

Summary of Contents for SmartRow DCX

Page 1: ...Vertiv SmartRow DCX Installation Manual...

Page 2: ...esponsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions Refer to other local practices or building codes as applicable for the corre...

Page 3: ...uence Overview 19 6 1 1 Staging the Vertiv SmartRow Equipment 19 6 1 2 Installing the Vertiv SmartRow Equipment 19 6 1 3 Connecting the Equipment 20 6 1 4 Installing Expansion Channels 20 6 1 5 Finali...

Page 4: ...9 1 Liebert CRV 31 9 2 UPSs and Rack PDUs 31 9 3 Electrical System 31 10 Technical Illustrations 33 Vertiv SmartRow DCX Installation Manual 4...

Page 5: ...sure control for outdoor ambient temperatures as low as 30 F 35 C provided that the total design range from minimum to maximum is 125 F 70 C or less For traditional DX applications Vertiv Liebert Lee...

Page 6: ...Vertiv SmartRow DCX Installation Manual 6 This page intentionally left blank...

Page 7: ...S Hazardous Voltage Present Note following instructions Consult user manual for additional information Indicates weight Indicates ground connection Indicates alternating current Vertiv SmartRow DCX In...

Page 8: ...Vertiv SmartRow DCX Installation Manual 8 This page intentionally left blank...

Page 9: ...rtiv SmartRow DCX racks may house critical IT equipment optional rack power distribution units and optional rack mounted UPS units Cooling air is supplied in the row by Liebert CRV thermal management...

Page 10: ...rtiv SmartRow DCX components 3 3 Liebert CRV Notes Does not include reheat or humidifier Includes a condensate pump drain field installed Factory installed leak detection Vertiv SmartRow DCX Installat...

Page 11: ...and 85 F 10 C and 30 C dry bulb and less than 60 F dew point 16 C It is not suitable for installation outdoors or in unconditioned spaces loading docks unconditioned warehouses garages etc A properly...

Page 12: ...ties based on 45 F 8 C entering water conditions with 10 F 6 C rise always use site specific water conditions when determining cooling unit net sensible capacity Table 4 1 Vertiv SmartRow DCX quick re...

Page 13: ...ity per Cooling Unit _______ kW From Table 4 1 on the previous page 6 Minimum Quantity of Liebert CRV Cooling Units ______ Cooling units Round up to whole number 7 Add 1 if desire N 1 cooling redundan...

Page 14: ...e UPS system If the cooling system is designed for N 1 redundancy be sure that each rack is within the region of influence of 2 or more Liebert CRVs with sufficient capacity This will ensure that if a...

Page 15: ...Table 4 4 Included spacing between system equipment 4 5 IT Equipment Deployment and Wiring Follow industry best practices when deploying IT equipment within the Vertiv SmartRow DCX To maintain good c...

Page 16: ...eed modulation range is raised at the factory Do not field adjust Do not run the Liebert CRV in a staged staggered or stand by configuration All Liebert CRVs must be operational at the same time Ensur...

Page 17: ...water glycol cooled systems Input power sufficient for Each Liebert CRV each requires a separate input power feed Liebert EXM ships as single input configuration but may be wired as dual input NOTE F...

Page 18: ...Row DCX Adhere to all warnings cautions and installation operating and safety instructions on the units and in their manuals Only properly trained and qualified personnel should move install operate o...

Page 19: ...nt install the gasketing and spacers included with the UPS equipment Tip Adjust all equipment leveling feet until the casters are just off the floor This will ensure proper fit of the skirting install...

Page 20: ...y set the 2T sensor DIP switches per the supplied instructions 4 Cable the Liebert CRV iCOM and monitoring card to the Vertiv SmartRow network switch 5 Cable the UPS monitoring card to the Vertiv Smar...

Page 21: ...ching button To engage the Emergency Power Off EPO press the button until it latches and the system shuts down To disengage the EPO pull out the EPO button When engaged all cooling units UPSs if wired...

Page 22: ...l normally closed relays in the fire suppression panel Once the timer expires the circuit returns to the Off position You can turn the timer up to a maximum of 2 hours if necessary to perform maintena...

Page 23: ...er expires the circuit is returned to its normal setting Off Note You can turn the timer up to a maximum of two hours if necessary to perform maintenance To continue the bypass operation just turn the...

Page 24: ...past the half hour mark again to continue the bypass 4 Reset the UPS that powers the Vertiv SmartRow DCX control circuit and fire suppression control circuit If the Vertiv SmartRow DCX is powered by...

Page 25: ...System Rack Supply has shut down 1 Turn Emergency Power Off Override timer beyond the 1 2 hour position see Figure 6 2 on page 22 and Vertiv SmartRow DCX Control Panel and Fire Suppression System tim...

Page 26: ...Vertiv SmartRow DCX Installation Manual 26 This page intentionally left blank...

Page 27: ...tRow DCX rack and their DIP switches set 10 Make sure that no cables are routed through any of the expansion channels 11 Liebert CRV has been started up and factory commissioned 12 Liebert EXM UPS has...

Page 28: ...Vertiv SmartRow DCX Installation Manual 28 This page intentionally left blank...

Page 29: ...Liebert CRV operation and maintenance manual SL 19800 shipped with the Vertiv SmartRow DCX and available at http www vertiv com en us support For assistance call 800 543 2378 UPS system has shut down...

Page 30: ...Vertiv SmartRow DCX Installation Manual 30 This page intentionally left blank...

Page 31: ...ips and Vertiv DCX racks call 800 222 5877 option 1 Outside North America call 00800 1155 4499 or e mail liebert upstech vertiv com For three phase UPS and power systems call 800 543 2378 outside Nort...

Page 32: ...Vertiv SmartRow DCX Installation Manual 32 This page intentionally left blank...

Page 33: ...10 TECHNICAL ILLUSTRATIONS The illustrations on the following pages are provided to assist with installation Vertiv SmartRow DCX Installation Manual 33...

Page 34: ...Vertiv SmartRow DCX Installation Manual 34 Figure 10 1 Vertiv SmartRow DCX System Submittal Overview typical...

Page 35: ...Vertiv SmartRow DCX Installation Manual 35 Figure 10 2 Vertiv SmartRow DCX 40kW One Line N 1 Redundant with Power...

Page 36: ...Vertiv SmartRow DCX Installation Manual 36 Figure 10 3 Vertiv SmartRow DCX 40kW One Line 2N Redundant with Power...

Page 37: ...Vertiv SmartRow DCX Installation Manual 37 Figure 10 4 Vertiv SmartRow DCX System Submittal Dimensions typical...

Page 38: ...Vertiv SmartRow DCX Installation Manual 38 Figure 10 5 Vertiv SmartRow DCX System Submittal Clearances typical...

Page 39: ...Vertiv SmartRow DCX Installation Manual 39 Figure 10 6 Vertiv SmartRow DCX System Submittal One Line typical...

Page 40: ...Vertiv SmartRow DCX Installation Manual 40 Figure 10 7 Vertiv SmartRow DCX System typical...

Page 41: ...Vertiv SmartRow DCX Installation Manual 41 Figure 10 8 Vertiv SmartRow DCX Assembly 1 typical...

Page 42: ...Vertiv SmartRow DCX Installation Manual 42 Figure 10 9 Vertiv SmartRow DCX Assembly 2 typical...

Page 43: ...Vertiv SmartRow DCX Installation Manual 43 Figure 10 10 Vertiv SmartRow DCX Assembly 3 typical...

Page 44: ...Vertiv SmartRow DCX Installation Manual 44 Figure 10 11 Vertiv SmartRow DCX Assembly 4 typical...

Page 45: ...Vertiv SmartRow DCX Installation Manual 45 Figure 10 12 Vertiv SmartRow DCX Fan Control vNSA...

Page 46: ...Vertiv SmartRow DCX Installation Manual 46 Figure 10 13 Vertiv SmartRow DCX Fan Control vNSA Cabling...

Page 47: ...Vertiv SmartRow DCX Installation Manual 47 Figure 10 14 Vertiv SmartRow DCX UPS Spacer Kit...

Page 48: ...Vertiv SmartRow DCX Installation Manual 48 Figure 10 15 Vertiv SmartRow DCX Liebert EXM Installation Pg 1...

Page 49: ...Vertiv SmartRow DCX Installation Manual 49 Figure 10 16 Vertiv SmartRow DCX Liebert EXM Installation Pg 2...

Page 50: ...Vertiv SmartRow DCX Installation Manual 50 Figure 10 17 Vertiv SmartRow DCX Liebert EXM Installation Pg 3...

Page 51: ...Vertiv SmartRow DCX Installation Manual 51 Figure 10 18 Vertiv SmartRow DCX Liebert EXM Installation Pg 4...

Page 52: ...Vertiv SmartRow DCX Installation Manual 52 Figure 10 19 Vertiv SmartRow DCX Liebert EXM Installation Pg 5...

Page 53: ...Vertiv SmartRow DCX Installation Manual 53 Figure 10 20 Vertiv SmartRow DCX Rack Expansion Channels Install pg 1...

Page 54: ...Vertiv SmartRow DCX Installation Manual 54 Figure 10 21 Vertiv SmartRow DCX Rack Expansion Channels Install pg 2...

Page 55: ...Vertiv SmartRow DCX Installation Manual 55 Figure 10 22 Vertiv SmartRow DCX Liebert CRV600 Expansion Channels Install pg 1...

Page 56: ...Vertiv SmartRow DCX Installation Manual 56 Figure 10 23 Vertiv SmartRow DCX Liebert CRV600 Expansion Channels Install pg 2...

Page 57: ...Vertiv SmartRow DCX Installation Manual 57 Figure 10 24 Vertiv SmartRow DCX Liebert CRV600 Expansion Channels Install pg 3...

Page 58: ...Vertiv SmartRow DCX Installation Manual 58 Figure 10 25 Vertiv SmartRow DCX Dimensions Fire Detection and Suppression 35 Cylinders...

Page 59: ...Vertiv SmartRow DCX Installation Manual 59 Figure 10 26 Vertiv SmartRow DCX Component Layout Fire Detection and Suppression 35 Cylinders...

Page 60: ...Vertiv SmartRow DCX Installation Manual 60 Figure 10 27 Vertiv SmartRow DCX Connections Fire Detection and Suppression 35 Cylinders...

Page 61: ...Vertiv SmartRow DCX Installation Manual 61 Figure 10 28 Vertiv SmartRow DCX Racks with Expansion Channels...

Page 62: ...Vertiv SmartRow DCX Installation Manual 62 Figure 10 29 Vertiv SmartRow DCX Liebert CRV600 with Expansion Channels...

Page 63: ...Vertiv SmartRow DCX Installation Manual 63 Figure 10 30 Vertiv SmartRow DCX Dimensions Liebert EXM 208V 480V with Expansion Channels...

Page 64: ...Vertiv SmartRow DCX Installation Manual 64 Figure 10 31 Vertiv SmartRow DCX Dimensions Liebert EXM BDC 208V 480V with Expansion Channels...

Page 65: ...Vertiv SmartRow DCX Installation Manual 65 Figure 10 32 Vertiv SmartRow DCX Dimensions Liebert EXM Battery Cabinet 600mm with Expansion Channels...

Page 66: ...Vertiv SmartRow DCX Installation Manual 66 Figure 10 33 Vertiv SmartRow DCX Server Rack Isometric Drawing...

Page 67: ...Vertiv SmartRow DCX Installation Manual 67 Figure 10 34 Vertiv SmartRow DCX Server Rack Outline Drawing...

Page 68: ...Vertiv SmartRow DCX Installation Manual 68 Figure 10 35 Vertiv SmartRow DCX Network Rack Isometric Drawing...

Page 69: ...Vertiv SmartRow DCX Installation Manual 69 Figure 10 36 Vertiv SmartRow DCX Network Rack Outline Drawing...

Page 70: ...Vertiv SmartRow DCX Installation Manual 70 Figure 10 37 Vertiv SmartRow DCX Control Panel and Fire Suppression Control Logic...

Page 71: ...Vertiv SmartRow DCX Installation Manual 71 Figure 10 38 Vertiv SmartRow DCX Control Panel and Fire Suppression Power Connections...

Page 72: ...Vertiv SmartRow DCX Installation Manual 72 This page intentionally left blank...

Page 73: ......

Page 74: ...names and logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness herein Vertiv Group...

Reviews: