Vertiv
|
NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA)
|
Rev. G
17
Figure 1:
Local Indicator Locations
Table 2:
Rectifier Module Indicators
Indicator
Normal State Alarm State
Alarm Cause
Power
(Green)
On
Off
No input voltage.
Internal input fuse open.
Flashing
The rectifier is being identified by the
controller.
Protection
(Yellow)
Off
On
AC input under/over voltage.
PFC output under/over voltage.
Moderate load sharing imbalance.
Rectifier not inserted into the slot
completely.
Rectifier over-temperature protection.
Rectifier in ECO Standby Mode when
ECO Mode is active in controller.
Flashing
Loss of communication with controller
(the rectifier can provide power).
Alarm
(Red)
Off
On
Severe load sharing imbalance.
Rectifier output disabled for any
reason, including overvoltage
shutdown and internal output fuse
open.
Rectifier addresses contradictory.
Flashing
One or both fans not operating
(rectifier shuts down).
RECTIFIER MODULE
Protection Indicator
(Yellow)
Alarm Indicator
(Red)
Power Indicator
(Green)