![Vertiv NetSure F1011259 Description And Installation Manual Download Page 38](http://html1.mh-extra.com/html/vertiv/netsure-f1011259/netsure-f1011259_description-and-installation-manual_1008115038.webp)
Vertiv™ NetSure™ External Distribution Box (EDB) Description and Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
28
Figure 11.6 Typical Power System LVD Connections to Alarm BLOCK 2 (Vertiv™ NetSure™ 512 DC Power System, Spec. No.
582137000 List 27, 582137000ZZ007 Shown. Others Similar.)
Red Wire to LVD+
Black Wire to LVD-
White Wire to LVD
AUX Contacts
P/N 60031373
(30 Feet)
Orange Wire to Orange Wire
Slate Wire to Slate Wire
Blue/White Wire to Blue/White Wire
P/N 60031372
Rear
Vertiv™ NetSure™ 512 DC Power System,
Spec. No. 582137000 List 27 (582137000ZZ007)
Shown. Others Similar.
Notes:
1. Factory installs links
on the factory wiring
side of terminal.
Factory Wiring Side
Customer Wiring Side
LVD+ LVD- LVD AUX
Contacts
CBA Alarm Signal to
DC Power System
Digital Input
LVD Coil
Block 1 and Block 2:
Wire Size Capacity:
20 AWG to 22 AWG.
Plug the two wire
harness connectors
labeled LVD1 together.
Strip the wire and crimp
P/N 140968 spade lug to
end of each wire.
Components removed in