Vertiv
|
NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
81
Table 9:
Programmable Relay Outputs – EIB
Programmable
Relay Output
EIB
Pin No.
Alarms Assigned to this
Relay (Default)
Alarms Assigned to this
Relay (Custom)
9
NO
J8-5
The relays may be
preprogrammed for specific
functions. Refer to the
configuration drawing (C-
drawing) supplied with your
system for your system’s
specific configuration.
COM
J8-3
NC
J8-1
10
NO
J8-6
COM
J8-4
NC
J8-2
11
NO
J9-5
COM
J9-3
NC
J9-1
12
NO
J9-6
COM
J9-4
NC
J9-2
13
NO
J7-6
COM
J7-4
NC
J7-2
NOTE!
The relays energize during an alarm condition, closing the contacts between the C and NO
terminals, and opening the contacts between the C and NC terminals.
Refer to the configuration drawing (C-drawing) supplied with your system for your system’s specific
relay labeling.