Vertiv
|
NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
112
Battery Connections to Distribution Cabinet Battery Busbars
DANGER!
Adhere to the “Important Safety Instructions” presented at the front of this document.
Battery may be connected to the battery busbars located in the distribution cabinet, as detailed in
, depending on site requirements.
Figure 67:
Battery Connections to Distribution Cabinet Battery Busbars
(4-Row Cabinet Shown,
Others Similar)
Battery
(Return Side)
Busbar
Battery
(Return Side)
Busbar
Battery
(Load Side)
Busbar
Battery
(Load Side)
Busbar
GND RTN
+24V SUPPLY
BATTERY AND BATTERY RETURN CONNECTIONS
(7 landings per polarity)
3/8-16 Captive Nuts on 1” Centers
(Customer must supply
additional hardware)
Maximum Lug Width: 1.88 inches
(unless otherwise noted).
Maximum Lug Width: 1.25 inches
(this location only).
Battery
(Return Side)
Busbar
Battery
(Load Side)
Busbar
Battery
(Return Side)
Busbar
Battery
(Load Side)
Busbar
BATTERY AND
BATTERY RETURN CONNECTIONS
(4 landings per polarity)
3/8-16 Captive Nuts on 1” Centers
(Customer must supply
additional hardware)
BATTERY AND
BATTERY RETURN CONNECTIONS
(4 landings per polarity)
3/8-16 Captive Nuts on 1” Centers
(Customer must supply
additional hardware)
1-Row Cabinet
2-Row Cabinet
3-Row and 4-Row Cabinets
Central Office
Ground
Central Office
Ground
Central Office
Ground