Chapter 4 Use Of The Controller 35
NetSure 531 AC1 Power Supply System User Manual
If the battery is configured and load current without instantly shocks, the system will operate under energy saving
mode, that is,
‘Save Enable’ is set to ‘Y’.
3. Advantage
Working on the best efficiency to save energy.
Balancing working hours of the rectifiers to prolong the lifetime of the rectifier.
In shutdown state, preventing rectifiers from damaged about AC inrush to reduce lightning fault.
4. Abnormal situation treatment
Switch off all the rectifiers when busbar voltage fails (DC over- voltage or low- voltage).
Switch on all the rectifiers when a rectifier alarm (Rect Not Respond) is generated.
Switch on all the rectifiers when an AC alarm (Mains Failure) is generated.
Switch on all the rectifiers automatically when the system has no controller or the communication is interrupted
between the rectifier and controller.
Delay implementation when the rectifier receives shutdown command, immediately execute when the rectifier
receives startup order.
The parameters of the energy saving are listed in Table 4-17.
Table 4-17 Energy saving parameters
Parameter
Range
Factory setting
Value description
Save
Enable
Y, N
N
It can be set to
‘Y’ when the battery is configured and load current without
instantly shocks
Cyc
Period*
1h ~ 8760h
48h
Time of rectifier under power-on state and power-off state, it can be set
according to actual requirement
Rect Work
30% ~ 90%
80%
Output capacity percentage. More rectifiers will startup to work when larger than
this setting percentage
Rect Limit
1 ~ 30
1
Minimum number of the rectifier
Note*: Cyc Period, Rect Work and Rect Limit are available only when
‘Save Enable’ is set to ‘Y’
4.9 Fast Settings
The Fast Settings is a sub-menu of the MAINMENU. At the MAINMENU page, press
▲ or ▼ to select Fast Settings,
then press ENT to confirm. After you input the correct password, the page shown in Figure 4-38 is displayed.
System Type:
48V/SET
Capacity: 600Ah
Figure 4-38 Fast Settings page
At the Fast Settings page, you can set the system type and battery capacity, as listed in Table 4-18.
Table 4-18 List of fast settings
Parameter
Range
Factory setting
Value description
System
Type
24V/100
24V/300
24V/500
24V/1000
24V/SET
48V/100
48V/300
48V/500
48V/1000
48V/SET
48V/SET
The system type of the controller has been set according to the actual
instance before the controller is delivered with power supply system. You
need not to change the value except that the controller is replaced with a
new one.
After changing the type, the controller will restart automatically and the other
parameters will resume the default. You need to reset and change some
parameters according to the battery and equipment configured with system
Capacity
50Ah ~ 5000Ah
300Ah
The capacity of the total battery strings. You should set this parameter
according to the actual battery configuration