Vertiv
|
NetSure™ 5100 Series -48 VDC Power System User Manual (UM582137200)
|
Rev. G
9
CUSTOMER DOCUMENTATION PACKAGE
This document (UM582137200) provides
User Instructions
for the NetSure™ 5100 Series -48 VDC Power
System: Model 5100, Spec. No. 582137200.
The complete Customer Documentation Package consists of…
NetSure
™
-48 VDC Power System Installation Manual
•
Power System Installation Instructions: IM582137200
NetSure
™
-48 VDC Power System User Manual
•
Power System User Instructions: UM582137200
NetSure
™
NCU Controller User Manual
•
NCU Controller User Instructions: UM1M830BNA
USB Drive with All Customer Documentation
•
Power System Installation Instructions: IM582137200
•
Power System User Instructions: UM582137200
•
Power System “System Application Guide”: SAG582137200
•
NCU Controller User Instructions: UM1M830BNA
•
Rectifier Instructions: UM1R482000e3
•
Engineering Drawings
-
SD582137200
-
T582137200
•
Also provided on the USB drive is a controller configuration drawing and the controller configuration
files loaded into the controller as shipped.
SYSTEM DESCRIPTION
-48 VDC @ up to 150 Amperes Power System
The NetSure™ 5100 DC Power System is an integrated power system containing rectifiers, intelligent control,
metering, monitoring, and distribution.
This power system is designed to power a load while charging a positive grounded battery. This power system
is capable of operating in a batteryless installation or off battery for maintenance purposes. The power system
is designed for operation with the positive output grounded.
The NetSure 5100 consists of the following components mounted in a 19” or 23” wide relay rack or cabinet rack.
Wall mounting options are also available.
Controller
NCU (NetSure Control Unit): The controller provides power system control (including optional low voltage
battery disconnect [LVBD] and low voltage load disconnect [LVLD] control), rectifier control (including a
charge control function), metering functions, monitoring functions, local/remote alarm functions, and