2.7. Pipe Outlet Position Size on Top Plate
The location and positioning dimensions of the inlet and outlet pipes of the unit top plate are shown in
ITEMS
DESCRIPTION
ITEMS DESCRIPTION
1
Drain
3
Refrigerant outlet
2
Inlet cable
4
Refrigerant inlet
Figure 2-8 Outlet Position of the Unit’s Top Plate
2.8. Installing the Unit
2.8.1. Installation Location Requirements
The position and spacing of the Vertiv
™
Liebert® XDO terminal mounted on the ceiling are determined by the heat density of
the heat dissipating cabinet. For specific spacing, please refer to the relevant drawings on site.
• The Liebert XDO terminal must be firmly installed at the ceiling. Therefore, the building structure of
the ceiling and the support of the existing building need to be reinforced.
• Ensure to stabilize the top of the suspension rod and ensure that all nuts are firmly tight.
2.8.2. Requirements for Handling Location
It is recommended to use a motorized forklift or manual forklift to transport the unit to the installation site, or at least two
trained personnel are needed to carry it. The location requirements for personnel handling the unit are shown in
.
To avoid the leakage or breaking of the piping, do not use the side panels or external piping of the unit to directly lift or move
the unit.