ITEMS
DESCRIPTION
ITEMS DESCRIPTION
1
Screw GB9074_13-88_M8 x 20
2
Hexagon head bolt GB/T 5782-2000_M8 x 80
Figure 2-5 Bottom Pallet Screw Fixing Position
2.4. Inspection
After unpacking, check whether the accessories are complete according to the packing list (the Vertiv™ Liebert® XDC
accessories list is shown in the following
), and check whether any part is obviously damaged.
If any part is found to be missing or damaged during inspection, or if any concealed damage is identified, it should be
reported immediately to the carrier, Vertiv local representative and product supplier.
Table 2-2 Liebert XDC Accessories List
Name
Specifications
Quantity
Usage
User manual
Paperback (A4 Booklet)
1
On-site reference use.
Engineering sight
glass
Connection size 16
2
To be welded on the main liquid piping at site, one for each
refrigerant piping system. It is use to see while charging
the refrigerant and to observe the state of the refrigerant
in the system.
L-shaped cabinet
parts and matching
screws
Screw specifications
GB819_1_2000_M5x12
4
If the Liebert XDC main unit is installed between the rows,
user can fix it with the adjacent cabinets by combining
the cabinets.
2.5. Installation Notes
1. The Liebert XDC main unit is recommended to be installed between the rows or on the floor of the equipment room or
the computer room. According to the diversified types of Vertiv™ Liebert® XD terminals, user can choose
Vertiv™ Liebert® XDH floor installation, Vertiv™ Liebert® XDO (ceiling mounted at cold aisle), Vertiv™ Liebert® XDV
placed on the server rack.
2. Prior to installing the unit, confirm whether the installation environment meets the requirements
(refer
Section 1.6 Environment Conditions
), and confirm whether the building need any modification to match the
requirement of pipeline’s layout, for more details consult Vertiv local representative.
3. The installation must strictly follow the design drawings, and reserve maintenance space for daily maintenance and
repairs. Refer to the engineering dimension drawing provided by the manufacturer.