Contacts terminals 82, 83 and 84 are activated by the condensate detection alarm.
•
T82 is used for normally open contact closure requirements.
•
T83 is common.
•
T84 is used when normally closed contact closure is required.
•
Contacts terminals 85, 86 and 87 are activated by the fan failure alarm.
•
T85 is for normally open contact closure requirements.
•
T86 is common.
•
T87 is used when normally closed contact closure is required. The condensate detection
alarm and the fan failure alarm operate independently of each other.
•
P66 and P67 are CAN bus ports.
Figure 4.30 Low-voltage connections for Liebert XDV smart modules
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
98