Branch Piping
Standard Run
Long Run *
Ten Port
186650G51
186553G51
Supply
inch (mm)
Outside Diameter (ODS)
1-1/8
1-3/8
Height (H)
8-3/4 (222)
8-3/4 (222)
Length (L)
6-3/4 (171)
6-7/8 (175)
Return
inch (mm)
Outside Diameter (ODR)
2-1/8
2-5/8
Height (H)
10-1/2 (267)
10-1/2 (267)
Length (L)
9-1/8 (232)
* Pipe runs greater than 60 equivalent feet
Table 3.12 Ten-port prefabricated piping legend
3.21 Liebert XD Flex Pipe Kit
Liebert XD Flex Pipe kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8,2.4 and 3 meters). Connection
style to the module end may be straight or 90 degrees with one-shot or removable connections.
Connection to the prefabricated piping assembly is a threaded coupler. For data on acquiring the correct
kit for your installation, see Table 3.13 below.
Description
Liebert XDV
Liebert XDCF
Liebert
XDO
Liebert XDH
Liebert XDR
One-Shot
Couplings
Removable
Couplings
One-Shot
Coupling
One-Shot
Coupling
One-Shot
Coupling
Removable
Couplings
One-Shot
Coupling
Removable
Couplings
4ft long
(1.2m), 0º
186568G4
187867G4
186568G4
2
186566G4
2 x
186566G4
2 x
187865G4
186566G4
187865G4
4ft long
(1.2m),
90º
186567G4
187866G4
—
186565G4
2 x
186565G4
2 x
187864G4
186565G4
187864G4
6ft long
(1.8m), 0º
186568G1
187867G1
186568G1
2
186566G1
2 x
186566G1
2 x
187865G1
186566G1
187865G1
6ft long
(1.8m),
90º
186567G1
187866G1
—
186565G1
2 x
186565G1
2 x
187864G1
186565G1
187864G1
8ft long
(2.5m), 0º
186568G3
187867G3
186568G33.
on the facing
page
186566G3
2 x
186566G3
2 x
187865G3
186566G3
187865G3
8ft long
(2.5m),
90º
186567G3
187866G3
—
186565G3
2 x
186565G3
2 x
187864G3
186565G3
187864G3
Table 3.13 Liebert XD Flex Pipe assemblies, supply and return
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
54
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......