7.11.4 Connecting to the Liebert XD Smart modules
Liebert XDO CANbus Port Locations
The Liebert XDO CANbus ports are located on the side of the electrical box. The cable from the Liebert
XDP or Liebert XDC side will be connected to Port P66. The leaving cable will be connected to Port P67.
See Figure 7.17 below.
Figure 7.17 Liebert XDO CANbus port locations
7.12 CANbus Termination
The last device in the chain must be terminated.
•
The remote temperature and humidity sensors are terminated at the factory.
•
The Liebert XD smart modules are not terminated at the factory. Improper termination will
cause communication errors.
7.12.1 Remote Temperature and Humidity Sensors Termination
The control board is terminated at the factory. If a remote sensor is the last device in the CANbus chain,
no changes are necessary. The termination jumper must be removed if a remote sensor is not the last
device in the CANbus chain. Refer to the Liebert XD module user manual for terminating procedures.
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
175
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......