WARNING! Risk of electric shock. Can cause injury or death. The DIP switches must be set
exactly as indicated in 9.4.3 on the previous page. Failure to correctly set the DIP switches may
result in an electrical or water hazard.
The DIP switch sets the capacity of the humidifier. If you replace the humidifier, set the DIP switches on
the circuit board based on the voltage and capacity of your unit shown in Table 9.3 below.
Voltage
SW1
SW2
SW3
SW4
Amps
3-ton Units
208/230
Off
On
Off
On
6.4
460
On
On
Off
Off
3.4
4-ton and 5-ton Units
208
On
On
On
Off
8.9
240
Off
On
On
Off
8.5
460
On
On
On
Off
4.5
575
On
On
Off
Off
3.4
Table 9.3 DIP switch settings for humidifier control board
9.4.4 Humidifier Troubleshooting
Symptom
Possible Cause
Check or Remedy
Humidifier
does not
operate
DIP switch not set to
enable humidifier option
See DIP-switch settings in Table 9.3 above.
Display does not show
humidification mode
Increase humidity-control setpoint
Defective board
Check the voltage at P35-1 on the unit's iCOM board, and P1-9 and P1-7 on the
humidifier-interface board for 24 VAC ±2 VAC.
If no voltage is detected, check wiring and/or replace board. Check the wiring from the
iCOM board to the humidifier-interface board.
Failed humidity sensor
Display shows "RET sensor invalid" warning. Check wiring from the
temperature/humidity board to the control board. Replace temperature/humidity
sensor if defective.
No water flow
Make sure that the switch is in "RUN" position. Check the humidifier water (including
filter screen) and check the nylon overflow line if the canister is full.
Canister fill rate does not
keep up with steam
output
Check the fill-valve screen opening and capillary tube for obstructions. Check the
water-supply pressure (minimum 10 psig).
Table 9.4 Steam generating humidifier troubleshooting guide
9.5 Condensate-drain and Condensate-pump System Maintenance
9.5.1 Condensate Drain
Check for and clear obstructions in tubing during routine maintenance.
Vertiv | Liebert® Mini-Mate™ Installer/User Guide
44
Summary of Contents for Liebert Mini-Mate MT036
Page 8: ...Vertiv Liebert Mini Mate Installer User Guide 8 This page intentionally left blank ...
Page 14: ...Vertiv Liebert Mini Mate Installer User Guide 14 This page intentionally left blank ...
Page 26: ...Vertiv Liebert Mini Mate Installer User Guide 26 This page intentionally left blank ...
Page 30: ...Vertiv Liebert Mini Mate Installer User Guide 30 This page intentionally left blank ...
Page 32: ...Vertiv Liebert Mini Mate Installer User Guide 32 This page intentionally left blank ...
Page 34: ...Vertiv Liebert Mini Mate Installer User Guide 34 This page intentionally left blank ...
Page 46: ...Vertiv Liebert Mini Mate Installer User Guide 46 This page intentionally left blank ...
Page 50: ...Vertiv Liebert Mini Mate Installer User Guide 50 This page intentionally left blank ...
Page 52: ...Vertiv Liebert Mini Mate Installer User Guide 52 This page intentionally left blank ...
Page 54: ...Vertiv Liebert Mini Mate Installer User Guide 54 This page intentionally left blank ...
Page 79: ...Vertiv Liebert Mini Mate Installer User Guide ...