2 TAP-OFF BOX MONITORING

If your Tap-Off Box is equipped with a monitoring option, there will be two RJ-45 jacks on the side of the
enclosure. The Tap-Off Box RJ-45 connections must be daisy-chained from Tap-Off Box to Tap-Off Box
with the final connection made at the End Feed Box that houses the gateway device. The last Tap-Off Box
in the daisy-chain must have a "Socomec" termination plug installed in the final RJ-45 jack.

NOTE: You can daisy-chain a maximum of 26 Tap-Off Boxes to the network gateway device, located in
the End Feed Box. If you need to daisy chain more than 26, a repeater Tap-Off Box is required. Consult
your sales representative for information on repeater Tap-Off Boxes.

NOTE: Before beginning to test or program any Digiware components in the Tap-Off Boxes, ensure
that your G-30 Module and U-30 Module are configured. The U-30 Module governs the baud rate and
parity for all I-modules. Alwayas check when testing I-modules that the baud rate programmed into the
U-30 carried over to the I-module.

To configure Tap-Off Boxes:

1. Power On the I-30 or I-60 using a Socomec RJ-45 cable, which is looped out from the U-30 Module. A

green light appears on the I-30 or I-60 Module to indicate it is powered On.

2. Connect the I-module to your laptop via USB – micro USB lead.
3. Click the

change profile button

in the upper right corner of Easy Config.

4. Log in to the Super User profile using password "sOcOmec".
5. Click

Get from Device.

6. Click the

Device

to configure, then click

Connect to Device

.

7. Select the

Product

Tab and verify the following information:

Identification – I-30 OR I-60 Serial Number

Type – Device Connected

Firmware Version – Latest firmware installed. You can check the latest firmware version on the
"Socomec" website. If firmware needs updated, see

Firmware Update

on page 9 for instructions.

The ‘Communication Configuration’ shown is :

Type – RS485.

Address – Set a unique Modbus address. The G-30 is 1, U-30 is 2, I-45 (if present) is 5.
Continue numbering I-modules starting at 10.

Baud Rate – Confirm match to U-30 settings.

Stop Bits – Confirm match to U-30 settings.

Parity – Confirm match to U-30 settings.

8. Select

Load

and confirm the following information:

Load Enabled – If CTs are connected, option to change settings.

Load Type – Select number of phases and amount of CTs.

Nominal Current – circuit rating associated with each CT.

CT Direction – If the CTs are reading an incoming or outgoing supply.

9. After the settings are updated, click

Final Action,

then click

Send to Device

.

2 Tap-Off Box Monitoring

5

Summary of Contents for Liebert MBX Busway

Page 1: ...Liebert MBX Busway System Optional Busway System Monitoring Installer User Guide ...

Page 2: ...isclaims all liability for damages resulting from use of this information or for any errors or omissions Refer to other local practices or building codes as applicable for the correct methods tools and materials to be used in performing procedures not specifically described in this document The products covered by this instruction manual are manufactured and or sold by Vertiv This document is the ...

Page 3: ...ENTS 1 Installation 1 1 1 End Feed Box Monitoring Setup 1 1 2 End Feed Box Ethernet Configuration 1 1 3 End Feed Box USB Configuration 2 2 Tap Off Box Monitoring 5 3 Web Portal Configuration 7 4 Firmware Update 9 i ...

Page 4: ...Vertiv Liebert MBX Monitoring Installer User Guide ii This page intentionally left blank ...

Page 5: ... any I modules The U 30 Module governs all I modules baud rate and parity Always check when testing I modules that the baud rate programmed into the U 30 carried over to the I module 1 2 End Feed Box Ethernet Configuration 1 Power ON the End Feed Box 2 Connect the G 30 Module to your laptop using a standard straight through CAT5 ethernet cable 3 Browse to www Socomec us download and install the la...

Page 6: ...d power cable Power only cables will not function To configure the End Feed Box monitoring device 1 Power On the End Feed Box and ensure that the G 30 and U 30 Modules are On 2 Connect the G 30 Module to your laptop using USB micro USB lead 3 Browse to www Socomec us download and install the latest Easy Config software 4 Click the Change Profile Button in the upper right corner of Easy Config 5 Lo...

Page 7: ...en click Connect to Device 13 Click Select All then click OK 14 Wait for the configuration to be sent to the device When the successful operation message pops up click OK 15 Remove the micro USB from the G 30 Module and insert it into the U 30 Module to configure the U 30 Module 16 Repeat Step 6 through Step 14 changing the address Slave ID to 2 for the U 30 Device NOTE Record the serial number of...

Page 8: ...Vertiv Liebert MBX Monitoring Installer User Guide 4 This page intentionally left blank ...

Page 9: ...light appears on the I 30 or I 60 Module to indicate it is powered On 2 Connect the I module to your laptop via USB micro USB lead 3 Click the change profile button in the upper right corner of Easy Config 4 Log in to the Super User profile using password sOcOmec 5 Click Get from Device 6 Click the Device to configure then click Connect to Device 7 Select the Product Tab and verify the following i...

Page 10: ...ding new Tap Off Box Modules to a busway run you must log into the G 30 module and re perform device discovery 1 Connect to the G 30 via Ethernet or USB 2 Click Device Detection Tab 3 Click New Discovery All newly configured I modules should appear 4 Click Final Action 5 Click Send to Device 6 Select the G 30 Module and click Connect To Device 7 Click Select All then Click Ok 8 Wait for the config...

Page 11: ...st log in into the Socomec web portal and update the configuration 1 Click the Change Profile Button in the upper right corner 2 Select Admin and enter password Admin 3 Click the Settings Gear Icon on the top left 4 Click Devices 5 Click Read Configuration 6 Confirm all modules appear 7 Click Save Configuration 3 Web Portal Configuration 7 ...

Page 12: ...Vertiv Liebert MBX Monitoring Installer User Guide 8 This page intentionally left blank ...

Page 13: ...ad the latest version of Socomec s Product Upgrade Tool and firmware version from the page above 2 Install the Product Upgrade Tool on your laptop 3 Connect the module to your laptop via USB micro USB lead 4 Open the Product Upgrade Tool program 5 Verify the module to be upgraded is displayed in the Master field 6 Click the Browse button and select the firmware ZIP file for the module 7 Click Upda...

Page 14: ...Vertiv Liebert MBX Monitoring Installer User Guide 10 This page intentionally left blank ...

Page 15: ...Vertiv Liebert MBX Monitoring Installer User Guide ...

Page 16: ... names and logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracyand completeness herein Vertiv Group Corp assumes no responsibility and disclaims allliability for damages resulting from use of this information or for any errors or omissions Specifications are subject to change without notice SL 7052...

Reviews: