The 1/0 dry contact port capacity. 125Vdc, 0.5A; 30Vdc, 7A
Pin11 and Pin12 reserves the corresponding terminals for configuring the REPO function. The REPO device
also needs the shielded cable to connect to the Normally Open remote REPO switch between the two
terminals. If not necessary. you should disconnect Pin9 and Pin 10.
Pin9 and Pin10 have been shorted before delivery.
The EPO action of the UPS will close the rectifier, inverter and static bypass, but it cannot disconnect
the UPS from mains input. If you want to disconnect the UPS completely, just disconnect the upstream
input MCB when generating the EPO.
In emergency conditions, close the REPO switch (prepared by users) to shut down the rectifier and
inverter, and the UPS is powered off. In normal condition, the REPO switch cannot cut off the UPS input
power. If a switch of electronic control tripping function is adopted at the UPS input, the REPO switch
helps the switch to trip and thus cuts off the UPS input power. The position of the REPO switch is
shown in Figure 1-3, and the REPO cable connection is shown in Figure 6-3.
REPO switc
Figure 6-
5
The cable connection procedures are as follows:
REPO cable connection
l Loosen the '11' and '12' connection terminals of the REPO port
;,:;
[T]
-0
0
REPO
plug
9
10
Jl
12
2. Insert the two ends of the copper core cables with the insulation leather peeled into the '11' and '12'
connection terminals of the REPO port, and press down the terminals. The REPO cable connection is
complete. Ensure that the REPO cable is firmly connected to avoid no action or wrong action of the
REPO caused by accidental dropping or infirm contact
3. For parallel UPSs, when connecting the REPO cable, users should parallelly connect '11' of the REPO
port with one end of the electronic switch, and parallel connect '12' with the other end of the electronic
switch.
When the REPO switch at the user end closes, the UPS generates an alarm and cut off the output
immediately, and the UPS will not return to the normal operation state automatically. At this point,
you must change the REPO switch state, and power on the UPS manually.
1. It
is
recommended to use 0.82mm
2
~ 0.33mm
1
(signal cable of 18A WG ~ 33AWG) copper core cable.
2. If the switch you have configured
is
of electronic control tripping function, when the REPO signal takes
action, you need to close the switch before restart the UPS.
Vertiv I Liebert� ITA2 ., 5kVA ~ 20kVA UPS I User Manual
·102
Summary of Contents for Liebert ITA2
Page 1: ...5 20 kVA User Manual...
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ...Product Model 5kVA 6kVA 10kVA 16kVA 20kVA...
Page 15: ...1 Product Introduction The...
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ...Battery...
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ...2 SingleUPSInstallationAnd Commissioning...
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ...BAT...
Page 59: ......
Page 61: ......
Page 64: ...3 ParallelUPSInstallationAnd Commissioning...
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ...4 Operation And Display Panel...
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 88: ...Maintain...
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ...5 UPS Operation Instructions...
Page 101: ......
Page 102: ......
Page 103: ...Confirm S Turn off UPS ol NO YES Log About Maintain...
Page 104: ...with...
Page 105: ......
Page 106: ......
Page 107: ...5 Press the key for several times to back to the main menu screen...
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 117: ...4...
Page 119: ......
Page 120: ...7 Maintenance...
Page 121: ......
Page 122: ......
Page 123: ...8 Options...
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 132: ......
Page 133: ...9 Attachment...
Page 134: ......
Page 135: ...Appendix 1 LCD Parameters Setting...
Page 136: ......
Page 137: ......
Page 138: ...Appendix 2Glossary...