background image

pag. 2

creased.

In these cases, Vertiv recommends a plenum  damper 

sized  600  x  400  mm  (Vertiv  code 134992) to be wall 

or window mounted.

3

 

---

 

Electrical

 

connections

3.1

 

---

 

Cautions

Before performing any operations on the electric parts, make 

sure that:

all electrical components are undamaged;
all terminal screws are  tight;

the supply voltage and frequency are as indicated on the 

unit;

the  automatic  switch 

QF1

  is  in  open position  (OFF), for 

units in “no emergency cooling version”.

the automatic switches 

QF1

 and 

QF3

 are in open position 

(OFF), for units in “emergency cooling version”.

there are no components under voltage.

3.2

 

---

 

Electrical

 

supply

Let the electrical power supply (not powered) pass through the 

holes placed in the back panel of the air conditioner (see from 

Fig. 1 to Fig. 4).

Caution:

  use screened cables for high voltage power supply, 

with suitable section, and route them to the electrical panel. 

Use copper conductors only.

Connect the power supply cable to the main switch QF1 inside 

the electrical panel. Connect the earth cable to the yellow--- 

-green clamp. The alarm contacts available in the different

ver-sions are located inside the electrical panel. For the

alarms de-scription see chapter 6.5 and manual of the

installation control.

3.3

 

---

 

User

 

interface

The control microprocessor board is inside the electric board 

and is connected with the user interface (remote display) that 

can be positioned inside the room as wished. The user 

interface (remote display), on a painted metal box, connected 

with the conditioner through a multi---pole screened cable, 

standard supplied.

The user interface is graphic type (with graphic display and 

keypad).

3.4

 

---

 

Emergency

 

cooling

 

version

(EFC 48 VDC and EFC 230 VAC)

When this option is available let pass the supply cable as 

de-scribed in par. 3.2 and connect them to switch QF3 

according to the diagram.

In the 48---VDC units respect the polarity “+” and “---”.

In the EFC 230 Vac units the emergency electrical line has to   

be always present.

3.5

 

---

 

Electrical

 

protection

Caution

:  For the electrical protection of the conditioner an 

adequate  switch  with  current  protection  must  be  installed  in 

the  power  supply  line.  For  the  selection  of  the  disconnect 

switch please refer to the Tab. 7.

4

 

---

 

Starting

 

and

 

stopping

4.1

 

---

 

First

 

start---up

 (or after a long halt)

Before starting the air conditioner do check if the power supply 

voltage  and  frequency  comply  with  those  indicated  on  the 

identification plate of the unit. After this, it is possible to power 

the unit operating on the main switches QF1 and QF3 

(only QF1 for units in “no emergency cooling version”),  that 

can be reached  removing  the  front  middle  panel.  For 

the  units equipped with microprocessor control, and after 

having operated on the switches to ensure a suitable power 

supply, it is possible to start and stop the unit following the 

instructions here below.

On

 the 

user

 interface

:

-

check that the fans are working correctly;

-

make  sure  that  the  temperature  is  guaranteed

and  the  compressor  and  the  heaters  (optional)  work

when re-quired;

-

make  sure  that  the  speed  adjuster  of  the  fan  of  the

con-densing section controls the fan operation (see chap.

7).

Note:

  turn the main switches QF1 and QF3 OFF (only QF1 for 

units  in  “no  emergency  cooling  version”)  only  if  the  unit  is 

stopped for a long time.

4.2

 

---

 

Start---up

 

with

 

low

 

outside

 

temperature

In case of low outside temperature (<0_C), the unit start---up is 

helped  by  the  delay  time  of  the  low  pressure  alarm 

activation,  within  which  the  pressures  in  the  refrigerating 

circuit reach the standard operation values.

5

 

---

 

Operation

The  unit  operation  is  completely  automatic.  The  below  se-

quence explains (with the assistance of Fig. 11 and Fig. 12--- -

Operation

 

diagram

)  how  the  unit  operates  (see  also  Fig.

 

13 

--- 

Refrigerating

 

diagram

):

1)

The temperature sensor, positioned inside the conditioned

room, informs the control about the condition of the air to

be conditioned.

2)

The control compares the information received with the set

values of 

Set

 

Point

 (= wished min. inner temperature)

and Proportional  Band  (and  differential  in  the  versions

with

Freecoolingoption),settingthe

 

conditioner

 

for

 

theair

treatment in the following modes:

Cooling

 (Fig. 11 and Fig. 12)

After  switching  the  unit  on,  the  evaporating  fan  is 

immediately started while the compressor is started when the 

temperature  of  the room  to be  conditioned  exceeds the set 

value. The con-densing  fan  is  automatically  started  when 

the  condensing  pressure  changes.  The  air  taken  in  by  the 

centrifugal  fan  enters  the  unit  through  the  suction  inlet, 

immediately passes through the filter and then the evaporator. 

The cold refrigerant flows in-side the pipes of the evaporator, 

thus cooling the air crossing it. The treated air is conveyed in 

the  conditioned  room  through  the  delivery  inlet.  The  heat 

taken  from  the  room  and  the  one  generated  by  the 

conditioner  motor  operation  are  disposed  through  the 

condenser placed in the lower part of the unit and hit, thanks 

to the fan, by  the  outside air.  The fan  operation  is

 managed 

with  Variex,  see  par.  5.1  as  a  function  of  the  con-design 

pressure. For the operation logics of the control see chapter 6

Pressing the On/Off Key ( ) the Unit ON/OFF window will 

appear. The unit is switched ON or OFF pressing the 

Increase ( ) or Decrease 

( ) 

Key for 3 seconds.;

 

Important!

  

I

t

is extremely important to consider the status of 

the digital input of the microprocessor control managing the 

unit ON ---OFF (see relevant handbook and wiring diagram).

Indeed, for the unit to start  the digital input must be bridged 

(see wiring diagram).
Check  that  there  are  no  active  alarms;  wait  until 

the system  reaches  the  standard  operation  and  then  make 

the following checks:

Summary of Contents for Liebert HPW Series

Page 1: ...Liebert HPW Outdoor Package Cooling System for Mobile Network Access Nodes User Manual English cod 265883 rev 31 01 2019...

Page 2: ......

Page 3: ...nce or spare parts read the identification label placed on the outside and inside of the unit IMPORTANT This manual may be subject to modification for complete and up to date information the user shou...

Page 4: ...g pag 2 4 1 First start up or after a long halt pag 2 4 2 Start up with low outside temperature pag 2 5 Operation pag 3 5 1 Adjustment of the condenser fan speed optional pag 3 5 2 Emergency cooling o...

Page 5: ...cabinet is made of heavy gauge galva nised steel panels painted on both sides with RAL7035 poly ester powder insulated with polyurethane foam fire proof class 1 Fixed panels are secured by water tight...

Page 6: ...hes to ensure a suitable power supply it is possible to start and stop the unit following the instructions here below On the user interface check that the fans are working correctly make sure that the...

Page 7: ...only unit 6 1 1 Control logic The control algorithm is based on a one step adjustment for the mechanical cooling with compressor the control manages all the activation delays so as to ensure the corre...

Page 8: ...3 1 1 2 2 3 Freecooling mode P Band Set Compressor cooling mode P Band _C Cooling Heating 6 5 Alarm control The two alarm contacts available on the terminal board of the electric board are 1 General...

Page 9: ...for units in emergency cooling ver sion 2 Remove the panels necessary for inspecting the refrigerat ing circuit 3 Connect a high efficiency vacuum pump to the needle valves Schr der on the gas and liq...

Page 10: ...sible and do not entail disproportionate cost a Prevent leakage of these gases and as soon as possible repair any detected leakage b Ensure that they are checked for leakage by certified per sonnel c...

Page 11: ...tions connected by refrigerant piping the label information will be on that part of the equipment which is initially charged with the refrigerant In case of a split system separate indoor and outdoor...

Page 12: ...10 0 10 0 10 Evaporator fan DC operative current OA 2 A 2 6 2 6 2 6 2 6 Evaporator fan DC max current FLA 3 A 2 6 2 6 2 6 2 6 Evaporator fan DC starting current LRA A 0 1 0 1 0 1 0 1 Electric heating...

Page 13: ...1 6 1 6 1 6 1 6 7 4 7 4 Evaporator fan DC power input 2 kW 0 10 0 10 0 28 0 45 0 45 0 45 Evaporator fan DC operative current OA 2 A 2 6 2 6 5 8 9 4 9 5 9 5 Evaporator fan DC max current FLA 3 A 2 6 2...

Page 14: ...erative current OA 2 A 9 5 9 5 17 2 16 3 Evaporator fan DC max current FLA 3 A 9 6 9 6 19 2 19 2 Evaporator fan DC starting current LRA A 0 1 0 1 0 1 0 1 Electric heating optional Heating capacity kW...

Page 15: ...rator fan AC power input 2 kW 0 14 0 14 0 14 0 14 Evaporator fan AC operative current OA 2 A 0 7 0 7 0 7 0 7 Evaporator fan AC max current FLA 3 A 0 7 0 7 0 7 0 7 Evaporator fan AC starting current LR...

Page 16: ...fan AC starting current LRA A 1 6 1 6 1 6 1 6 7 4 7 4 Evaporator fan AC power input 2 kW 0 15 0 15 0 47 0 48 0 48 0 48 Evaporator fan AC operative current OA 2 A 0 7 0 7 2 3 2 3 2 3 2 3 Evaporator fan...

Page 17: ...put 2 kW 0 49 0 49 0 78 0 80 Evaporator fan AC operative current OA 2 A 2 4 2 4 3 9 3 9 Evaporator fan AC max current FLA 3 A 2 4 2 4 4 8 4 8 Evaporator fan AC starting current LRA A 9 6 9 6 19 2 19 2...

Page 18: ...oling unit version Differential current protection switch I nn 0 03A Minimum cable sizing 2 poles 4 poles Main line power supply 230V 1Ph 50Hz 400V 3Ph N 50Hz Unit EFC DC line power supply 48VDC main...

Page 19: ...e switch HP STOP 28 0 bar START 20 0 bar fixed settings Manual reset pressing the push button Fan speed controller BV optional SET CUT OFF 21 2 bar standard factory set 15 0 bar optional set MAX SPEED...

Page 20: ...230 60 50 15 828 15 858 100 380 380 380 380 70 370 45 TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW 450 N 5 5 holes 8 for conditioner fixing Electrical supply Conditioned air inlet Condition...

Page 21: ...8 15 828 15 858 60 50 460 1230 100 380 380 380 380 70 450 N 5 5 holes 8 for conditioner fixing TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW Conditioned air inlet Conditioned air outlet Cond...

Page 22: ...960 15 990 1401 445 50 445 100 390 390 390 390 241 1901 N 5 5 holes 8 for conditioner fixing Lift with eye bolts Electrical supply TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW Conditioned...

Page 23: ...60 990 50 640 43 370 970 370 148 100 390 390 390 390 241 N 5 5 holes 8 for conditioner fixing Electrical supply Lift with eye bolts TOP VIEW FRONT VIEW REAR VIEW SX SIDE VIEW DX SIDE VIEW Conditioned...

Page 24: ...nd Operational B E areas 90o D A C E HPW Shelter PROTECTIVE ROOF F HPW A mm B mm C mm D mm E mm F mm S Models min 900 min 3500 800 450 min 500 0 M Models min 900 min 900 932 640 min 2000 0 No minimum...

Page 25: ...pag 21 Fig 6 Lifting system Liebert HPW Liebert HPW WM05 06SO SD Liebert HPW WM06 08 10 13 15MO MD SHACKLES NOT SUPPLIED EYE BOLTS NOT SUPPLIED...

Page 26: ...pag 22 Fig 7 Holes on the wall Liebert HPW models WM05 06SO SD 33 390 17 40 40 140 49 760 49 390 770 390 min 200 mm Installation of 1 unit Installation of 2 units SECTION...

Page 27: ...3 Fig 8 Holes on the wall Liebert HPW models WM06 08 10 13 15MO MD 50 890 50 390 950 390 33 390 40 350 190 min 200 mm Installation of 1 unit Installation of 2 units SECTION 350 107 WM 13 15 57 WM 06 0...

Page 28: ...pag 24 Fig 9 Sealing Liebert HPW models Insulating rubber mounted between the unit and the shelter External sealing with silicone after you have fixed the unit...

Page 29: ...pag 25 Fig 10 Correct procedure for the bending of the air inlet and outlet duct...

Page 30: ...agram Liebert HPW models WM05 06SO SD OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE Freecooling Compressor cooling Freecooling Compressor cooling Exhaust air outlet from left lateral pan...

Page 31: ...m Liebert HPW models WM06 08 10 13 15MO MD Upflow version OUTSIDE Freecooling Compressor cooling OUTSIDE OUTSIDE OUTSIDE Freecooling Compressor cooling Exhaust air outlet from left lateral panel INSID...

Page 32: ...5 6 HP LP 11 POS DESCRIPTION POS DESCRIPTION 1 Compressor 7 Thermostatic expansion valve 2 High pressure switch HP 8 Evaporating coil 3 Condenser fan 9 Evaporator fan 4 Condensing coil 10 Low pressur...

Page 33: ...rd Le Fabricant d clare que ce produit est conforme aux directives Europ ennes El Fabricante declara que este producto es conforme a las directivas Europeas O Fabricante declara que este produto est e...

Page 34: ...red trademarks of Vertiv Co All other names and logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accurac...

Reviews: