pag. 15
Tab. 8 -- Settings
Component
Setting
Notes
Low pressure switch (LP)
STOP: 1.0 bar
START: 2.0 bar
(fixed settings)
Automatic reset
High pressure switch (HP)
STOP: 28.0 bar
START: 20.0 bar
(fixed settings)
Manual reset pressing
the push button
Fan speed controller (BV)
(optional)
SET (CUT---OFF):
•
21.2 bar
(standard factory set)
•
15.0 bar
(optional set)
MAX. SPEED:
•
25.0 bar
(standard factory set)
•
18.8 bar
(optional set)
P. BAND: 3.8 bar
(for the adjustment refer to the
instructions supplied with the machine)