Summary of Contents for Liebert GXT MT+ CX 1K

Page 1: ......

Page 2: ...and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 4 3 Operations 5 3 1 Button operation 5 3 2 LCD Panel 5 3 3 Audible Alarm 7 3 4 LCD display wordings index 7 3 5 UPS Setting 7 3 6 Operating Mode D...

Page 3: ...ay that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect...

Page 4: ...rvise operations Unauthorized persons must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur b...

Page 5: ...iginal package in a safe place for future use 2 1 Rear panel view GXT MT CX 1K SB GXT MT CX 2K SB GXT MT CX 3K SB GXT MT CX 1K GXT MT CX 2K GXT MT CX 3K 1 AC input 2 Input circuit breaker 3 USB commun...

Page 6: ...ation port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through PC The UPS is equipped with intelligent slot perfect for either SNMP...

Page 7: ...ds to turn off the UPS UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm...

Page 8: ...frequency battery voltage load information and internal temperature Vac input output voltage Vdc battery voltage Hz frequency load level C F temperature Load information Indicates the load level by 0...

Page 9: ...isplay content Meaning ENA Enable DIS Disable ESC Escape b L Low battery O L Overload N C Battery is not connected O C Overcharge C H Charger b F Battery fault b V Bypass voltage range W T Waiting F U...

Page 10: ...the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Output frequency setting Interface Setting Parameter 2 Output frequency setting You may set the initial...

Page 11: ...om 0 999 in battery mode 0 When setting as 0 the backup time will be only 10 seconds 999 When setting as 999 the backup time setting will be disabled 07 Battery total AH setting Interface Setting Set...

Page 12: ...ll bypass voltage to output for energy saving Frequency Converter mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still...

Page 13: ...age too low 28 Bus short 05 x Over temperature 41 x Inverter soft start fail 11 x Over load 43 Inverter voltage high 12 x Charger failure 45 x 3 8 Warning indicator Warning Indicator Alarm Word Icon f...

Page 14: ...wice every second UPS is overload Remove excess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from...

Page 15: ...epair the DC DC mosfet will damage 5 Storage and Maintenance Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exce...

Page 16: ...ss when the utility is normal 130 UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal Current Crest Ratio 3 1 Harmonic Distortion 3 THD Linear Load 6 THD No...

Page 17: ...battery mode or transfer to bypass when the utility is normal 130 UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal Current Crest Ratio 3 1 Harmonic Disto...

Page 18: ...perature range of 0 C to 45 C for UPS optimal operation For every 5 C above 45 C the UPS will derate 12 of nominal capacity at full load The highest working temperature requirement for UPS operation i...

Page 19: ...of the UPS and 300mm in the back and two sides of the UPS for heat dissipation and easy maintenance 6 Connect To Transformer Please do NOT connect transformer to output of the UPS Otherwise it will ca...

Page 20: ...se UPS internal fault It s recommended to add one breaker between positive pole of battery pack and positive pole of external battery connector in UPS to prevent damage to battery packs from internal...

Page 21: ...19...