Table 5
Input dry contacts—J26
Pin
Name
Description
1
RIB_STATUS
Rectifier Input Breaker Status (Short for RIB Closed)
3
GND_DRY
Dry Ground
5
BIB_STATUS
Bypass Input Breaker Status (Short for BIB Closed)
7
GND_DRY
Dry Ground
9
LEGACY_MBB
Legacy Maintenance Bypass Breaker Status (Open for MBB Closed)
11
GND_DRY
Dry Ground
13
LEGACY_MIB
Legacy Maintenance Isolation Breaker Status (Short for MIB Closed)
15
GND_DRY
Dry Ground
17
GND_DRY
Dry Ground
19
MIB_STATUS
Maintenance Isolation Breaker Status (Open for MIB Closed)
21
MBB_STATUS
Maintenance Bypass Breaker Status (Short for MBB Closed)
23
GND_DRY
Dry Ground
25
—
N/A
27
RS485+ Channel #1
29
UT1_485-
RS485+ Channel #1
31
GND_MON
Monitor Ground
2
GEN_MODE
Generator Mode (N.O.)
4
GND_DRY
Dry Ground
6
TMP_BATT_IN
Battery Temperature
8
+12V_DRY
+12V Power
10
—
N/A
12
GND_DRY
Dry Ground
14
ENV_DET
Environment Room Temperature (N.O.)
16
GND_DRY
Dry Ground
18
CHG_SHUT
Charger Shutdown (N.O.)
20
GND_DRY
Dry Ground
22
MOB_STATUS
Module Output Breaker Status (Open for MOB Closed)
24
GND_DRY
Dry Ground
26
—
N/A
28
RS485+ Channel #2
30
UT2_485-
RS485+ Channel #2
32
—
N/A