A standard B-type USB port is provided to allow connection to a computer or network server. The USB
port can be used to communicate with the GXT4 configuration program (see section

Configuration

Program

on page 44 for details) or Liebert MultiLink (see

Liebert MultiLink

on page 43 for description)

that is provided on the CD that is included with the UPS.

6.2.1 Configuration Program

The configuration program is on the Liebert GXT4 CD and can be used instead of making configuration
setting changes from the LCD panel. The configuration program communicates to a computer running a
Microsoft® Windows® operating system via the included USB cable.

For most users, the factory-default settings are adequate. This section give a brief overview of the
features and parameters that are available for modification, as well as the factory-default settings. Should
any changes be necessary, refer to the Configuration Program User Manual that is located on the
included CD for further details.

The configuration program allows these features of the GXT4 to be changed:

Change and set the display language

Enable/Disable Auto-Restart (default is Enable)

Select frequency converter operation with a fixed output frequency of 50 Hz or 60 Hz, bypass
disabled (default is Auto-Select with bypass enabled)

Set the Low Battery Warning alarm time from 2 to 30 minutes (default is 2 minutes)

Enable/Disable the Auto-Battery test (default is Enable)

Enable/Disable Auto-Restart after removing Remote shutdown (default is Disable)

Set the wiring mode of Remote shutdown (default is normally open)

Set the Auto-Enable output after remote shutdown (default is Disable)

Set the Auto-Battery test to 8, 12, 16, 20, or 26 weeks (default is 8 weeks)

Select the number of external battery cabinets connected to the UPS to adjust the remaining
run time calculated by Vertiv™ software products (default is zero)

Select one of multiple output voltages to match various voltages.

UPS MODEL

FACTORY DEFAULT SETTING

OUTPUT VOLTAGE OPTION

All models

230 VAC

220V, 230V, 240V

Table 6.1 Output voltage option

NOTICE

The output voltage settings cannot be changed while the UPS is On and powering connected
loads.

NOTE: This program is compatible with UPS models beginning with ‘GXT4,’ as in ‘GXT4-3000RT230.’ It
is not compatible with earlier versions of the Liebert GXT UPS.
A computer running Microsoft® Windows 2000®, Windows XP®, Windows Vista®, Windows 7 or
Windows 8 is required to set up and run the configuration program.

Vertiv

| Liebert GXT4 Installer/User Guide |

44

Summary of Contents for GXT4-10000RT230

Page 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA Installer User Guide...

Page 2: ...any installation or operational issues with your product check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures For additional assistance visi...

Page 3: ...ual Bypass Mode 18 2 8 3 Battery Mode 18 2 8 4 Battery Recharge Mode 18 2 8 5 Frequency Converter Mode 19 2 8 6 Active ECO Mode 19 3 Installation 21 3 1 What s Included 21 3 2 Unpacking and Inspection...

Page 4: ...ypass 42 6 Communication 43 6 1 Liebert IntelliSlot Communication Cards 43 6 1 1 Liebert MultiLink 43 6 2 USB Port Communication 43 6 2 1 Configuration Program 44 6 3 Terminal Block Communication 45 6...

Page 5: ...9 Specifications 57 9 1 Auto Learning Battery Run Times 62 Appendices 63 Appendix A Technical Support 63 Vertiv Liebert GXT4 Installer User Guide 5...

Page 6: ...Vertiv Liebert GXT4 Installer User Guide 6...

Page 7: ...ry live voltage presenting an electric shock hazard To ensure human safety and normal UPS operation the UPS must be properly grounded before use When the UPS is connected to an IT power distribution s...

Page 8: ...t and recycle batteries in accordance with local regulations Determine if the battery is inadvertently grounded If it is inadvertently grounded remove the source of the ground Contact with any part of...

Page 9: ...ility at its end of life Do not dispose of this product as unsorted municipal waste Follow local municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste e...

Page 10: ...Vertiv Liebert GXT4 Installer User Guide 10 This page intentionally left blank...

Page 11: ...D for user friendly operation and local monitoring and configuration of operational parameters Flexible network management with Liebert MultiLink software Fan fault self inspection and automated diagn...

Page 12: ...ont view NO DESCRIPTION 1 Upper bezel 2 Operation and display panel 3 Lower bezel and battery access door 2 4 Rear Panel Features The rear panel of the Liebert GXT4 has these features Liebert IntelliS...

Page 13: ...aker 5 C19 output power receptacles 12 Maintenance bypass breaker 6 External battery connector 13 C13 output receptacles 7 IT Power System access cover 14 Output circuit breakers NOTE Hard wired and h...

Page 14: ...telliSlot Unity DP card 12 Maintenance bypass breaker 6 IT Power System Access Cover 13 REPO 7 Knockouts for hard wired power input and output 14 Terminal block communication 2 5 Removable Power Distr...

Page 15: ...ry packs behind a battery access door on the front of the unit Each internal battery pack is fitted with a connector to link to the UPS GXT4 10 000 VA battery pack shown is shown in the figure 5000 VA...

Page 16: ...regulated DC power for use by the inverter while ensuring that the wave shape of the input current used by the UPS is near ideal Extracting this sine wave input current achieves two objectives Effici...

Page 17: ...ndicate the diagnosed problem To manually transfer the connected load from the inverter to bypass press the Standby Manual Bypass button once and hold it for about 2 seconds 2 7 8 Maintenance Bypass T...

Page 18: ...ps sound every 5 seconds to warn that the battery is getting low this Low Battery Warning is user configurable In Battery Mode the battery indicator will illuminate and the LCD will show the prompt ut...

Page 19: ...hile the UPS is operating Voltage may still be present even when the AC input indicator is Off 2 8 6 Active ECO Mode All Liebert GXT4 models can operate in Active ECO Mode In this mode the connected e...

Page 20: ...Vertiv Liebert GXT4 Installer User Guide 20 This page intentionally left blank...

Page 21: ...rack mounting hardware including screws handles and mounting rail kit not included with E models 3 2 Unpacking and Inspection Unpack the UPS and conduct the following checks Inspect the UPS for shippi...

Page 22: ...support bases out of the accessories box Figure 3 1 Support bases NO DESCRIPTION 1 Support bases 2 Spacers with connectors 2 If optional Liebert external battery cabinets will be connected take out th...

Page 23: ...d as near the bottom of a rack as possible If placed too high it can make the rack top heavy and prone to tipping over For unit weights see Specifications on page 57 3 5 Installing External Battery Ca...

Page 24: ...e instructions included with the slide rails 3 Use the enclosed support bases for the tower option to prevent tip over One additional set of support base extensions ships with each EBC 4 Verify the th...

Page 25: ...utility input power must be disconnected 3 6 1 Installing the Power Distribution Box 1 Align the connectors and press the power distribution box onto the UPS 2 Hold the box firmly against the UPS and...

Page 26: ...s diagram Terminal Block Connections Conduit entry holes are provided on the rear and side of the box Input and output wiring should not share the same conduit We recommend using strain relief when in...

Page 27: ...e main menu select CONTROL then press Enter b Select TURN ON OFF and press Enter c Select TURN ON UPS BYPASS and press Enter The UPS transfers the connected loads to the internal bypass For help refer...

Page 28: ...figuring an IT Power System 1 Remove screws on the IT Power System Access Cover as shown in the figure 2 Disconnect the connectors as shown in the figure 3 Install the IT Power System Access Cover and...

Page 29: ...NO DESCRIPTION 1 Remove screws 2 IT power system connectors Vertiv Liebert GXT4 Installer User Guide 29...

Page 30: ...Vertiv Liebert GXT4 Installer User Guide 30 This page intentionally left blank...

Page 31: ...indicator 6 Enter button 2 Inverter indicator 7 Down button 3 Battery indicator 8 Up button 4 Bypass indicator 9 Escape button 5 ECO mode indicator 10 LCD panel 4 1 LED Indicators The LED indicators...

Page 32: ...input data field before confirming Up Pressing this button can move the cursor up or increase the value displayed in the input data field When a menu is displayed on several screens pressing the butt...

Page 33: ...4 4 Menu Structure The menu structure of the the LDC display is shown in the following figure Figure 4 2 Menu structure Vertiv Liebert GXT4 Installer User Guide 33...

Page 34: ...y or Bypass will be indicated by the LED indicators If no control button ESC Up Down Enter is pressed for 2 minutes the LCD will enter the screen saver mode back light turns off It will remain off unt...

Page 35: ...firm the settings Outlet1 Outlet Setting screen Select MAIN MENU 2 CONFIGURATION 4 OUTLET1 to enter the OUTLET1 screen This menu has two sub menus Select 2 Outlet Setting and press the Enter button to...

Page 36: ...ub menu TURN ON OFF screen Select MAIN MENU 3 CONTROL 1 TURN ON OFF to enter the TURN ON OFF screen This screen shows one of two displays TURN ON UPS and TURN OFF UPS depending on the state of the UPS...

Page 37: ...mode UPS Self Test Successful The UPS self test is successfully performed UPS Shutdown Command Received The UPS shut down was initiated through communication UPS Turn Off The UPS shuts down and has no...

Page 38: ...nsfers to bypass UPS Maintenance Bypass Output The UPS transfers to maintenance bypass AC input not qualified cannot start UPS The utility power is not qualified the inverter cannot be powered up Outp...

Page 39: ...he operation and display panel lights up and the alarm sounds continuously If a fault occurs 1 Enter the ALARM CONTROL screen and select AUDIBLE ALARM ON or AUDIBLE ALARM OFF to switch the alarm On or...

Page 40: ...Vertiv Liebert GXT4 Installer User Guide 40 This page intentionally left blank...

Page 41: ...it 3 The UPS will begin the startup sequence once AC power is present NOTE The UPS will sound an audible alarm this is normal 4 On the LCD press either the Up or Down button once then press the Enter...

Page 42: ...AC power and the UPS will completely shut down in approximately 15 seconds 5 6 Disconnecting Input Power from the GXT4 1 After the UPS has been shut down as detailed in Shutting Down the GXT4 on page...

Page 43: ...e network and or building management system The Liebert IntelliSlot UNITY card also enables monitoring external temperature humidity and contact closure inputs using external sensors Follow instructio...

Page 44: ...uency converter operation with a fixed output frequency of 50 Hz or 60 Hz bypass disabled default is Auto Select with bypass enabled Set the Low Battery Warning alarm time from 2 to 30 minutes default...

Page 45: ...Mode Shutdown can be performed using a switch mounted at a remote location and connected to the pins in terminal 3 NOTE Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdo...

Page 46: ...his timer cannot be stopped once triggered If the mains power returns during this countdown the GXT4 will still shut down and must remain shut down for 10 seconds Whether the UPS turns back On when th...

Page 47: ...h system fail safe 2 Opening the REPO connection disables the UPS Manual restart using the front panel is required after the REPO connection is closed again CAUTION To maintain safety SELV barriers an...

Page 48: ...Vertiv Liebert GXT4 Installer User Guide 48 This page intentionally left blank...

Page 49: ...cycle batteries in accordance with local regulations Determine if the battery is inadvertently grounded If it is inadvertently grounded remove the source of the ground Contact with any part of a groun...

Page 50: ...incorrect type Dispose of used batteries according to the instructions 1 Remove the front plastic bezel cover from the UPS 2 Loosen and remove the screws on the battery door as shown in Figure 7 1 be...

Page 51: ...battery wire and internal battery pack back into the UPS 10 Reattach the front battery door with the 6 screws 11 Reattach the front plastic bezel cover to the UPS NOTE The internal battery pack is ho...

Page 52: ...ve or Technical Support Check if the battery is discharging When the utility input is normal the battery should not discharge If the UPS is operating in Battery Mode stop and contact your Vertiv repre...

Page 53: ...Reduce the load and contact technical support Inverter Out of Order The inverter is faulty Contact technical support Battery Weak Bad The battery is bad or weak Replace the battery Output Short Circu...

Page 54: ...rt the unit Battery indicator is illuminated UPS is not plugged in UPS is operating from battery mode Ensure UPS is securely plugged into the wall receptacle UPS input protection fuse has blown opened...

Page 55: ...se are located in several places for your ease of location on the top panel rack mount orientation the left side tower orientation the rear panel on the front of the unit behind the front plastic beze...

Page 56: ...Vertiv Liebert GXT4 Installer User Guide 56 This page intentionally left blank...

Page 57: ...VAC 280VAC Input Frequency Without Battery Operation 40 70Hz Input Power Connection PD2 CE6HDWRMBS Standard See 1 4 Removable Power Distribution Box PD2 CE10HDWRMBS Standard See 1 4 Removable Power Di...

Page 58: ...at 1 meter from the front or sides Agency Safety IEC62040 1 2008 version GS mark EMI EMC C Tick EMC IEC EN AS 62040 2 2nd Ed Cat 2 Table 6 ESD IEC EN EN61000 4 2 Level 4 Criteria A Radiated Susceptib...

Page 59: ...Backup Time See Table 9 4 below Environmental Operating Temp C F 0 to 40 32 to 104 Storage Temp C F 15 to 50 5 to 122 Relative Humidity 0 95 non condensing Operating Elevation Up to 1000m 3280 83 ft a...

Page 60: ...12 Internal Battery 2 External Battery Cabinets 10 476 431 327 20 254 207 164 30 191 158 103 40 146 113 76 50 119 89 56 60 94 69 44 70 72 56 37 80 63 47 29 90 56 42 24 100 47 37 22 Internal Battery 3...

Page 61: ...224 176 106 70 184 148 87 80 163 125 74 90 148 114 60 100 125 103 55 Internal Battery 6 External Battery Cabinets 10 1367 1248 826 20 750 601 409 30 547 448 257 40 416 322 192 50 338 256 151 60 270 21...

Page 62: ...ated run time calculation only under certain conditions The UPS must have a steady load that is greater than 20 The UPS must be at 100 charge at the start of a battery discharge The battery discharge...

Page 63: ...unter with your Liebert product Please call or e mail us Technical support e liebert upstech vertivco com p 1 800 222 5877 menu option 1 Monitoring support e liebert monitoring vertivco com p 1 800 22...

Page 64: ...Vertiv Liebert GXT4 Installer User Guide 64 This page intentionally left blank...

Page 65: ......

Page 66: ...logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracyand completeness herein Vertiv Co assumes no re...