8.1.2 Audible Alarm
An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS
operating status. The audible alarm will sound as described in the following table.
CONDITION
ALARM
Battery discharge
Half-second beep every 10 seconds
Low battery
Two half-second beeps every 5 seconds
UPS fault, load on bypass
1-second beep every 4 seconds
UPS fault, no power to load
Continuous
Overload
Half-second beep every half second
Battery replacement
2-second beep every 2 minutes
Battery loss
Continuous
Wiring problem (loss of proper grounding for UPS)
Continuous
Bypass reminder
1-second beep every 60 seconds
Table 8.2 Audible alarm description
8.2 Troubleshooting UPS Issues
In the event of an issue with the UPS, refer to the following table to determine the cause and solution. If
the fault persists, contact Vertiv™ Technical Support. See
Technical Support
on page 63
PROBLEM
CAUSE
SOLUTION
UPS fails to
start
UPS is short-circuited or
overloaded
Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure
loads are not defective or shorted internally.
Batteries are not charged
enough or not connected
Check to ensure the internal battery is connected. If it is not, make the connection and try to start the
unit. If the battery is connected, leave the UPS connected to input power for 24 hours to recharge
batteries, then try to start the unit.
Battery
indicator is
illuminated
UPS is not plugged in
UPS is operating from battery mode. Ensure UPS is securely plugged into the wall receptacle.
UPS input protection fuse has
blown/opened
UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then
restart UPS.
Mains power is out of
tolerance
UPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is
within acceptable limits for UPS.
UPS has
reduced
battery
backup time
Batteries are not fully charged
Keep UPS plugged in continuously at least 24 hours to recharge batteries.
UPS is overloaded
Check load level indicator and reduce the load on the UPS.
Batteries may not be able to
hold a full charge due to age
Replace batteries. Contact your local dealer, Vertiv™ representative or Technical Support for
replacement battery kit.
Battery
indicator is
flashing.
Battery source is not available;
continuous horn.
Check battery connections, completely power down and restart UPS.
NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery
test is performed.
Bypass
indicator is
flashing.
Because the voltage or
frequency is outside
acceptable limits, the bypass
is disabled.
The AC input powers the PFC input and serves as the bypass source. If the AC is present but the
voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be
disabled and this indicator will flash, indicating that the bypass is unavailable.
Table 8.3 Troubleshooting table
Vertiv
| Liebert GXT4 Installer/User Guide |
54
Summary of Contents for GXT4-10000RT230
Page 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA Installer User Guide...
Page 6: ...Vertiv Liebert GXT4 Installer User Guide 6...
Page 10: ...Vertiv Liebert GXT4 Installer User Guide 10 This page intentionally left blank...
Page 20: ...Vertiv Liebert GXT4 Installer User Guide 20 This page intentionally left blank...
Page 30: ...Vertiv Liebert GXT4 Installer User Guide 30 This page intentionally left blank...
Page 40: ...Vertiv Liebert GXT4 Installer User Guide 40 This page intentionally left blank...
Page 48: ...Vertiv Liebert GXT4 Installer User Guide 48 This page intentionally left blank...
Page 56: ...Vertiv Liebert GXT4 Installer User Guide 56 This page intentionally left blank...
Page 64: ...Vertiv Liebert GXT4 Installer User Guide 64 This page intentionally left blank...
Page 65: ......