GEIST™ POWER FAILURE SENSOR

Quick Installation Guide

  

VM1055/590-2254-501A

  

LED turns on and the flashing 

LED stays solid on, indicating 

that the sensor is ready.

4. Use the remote monitoring unit 

to test the sensor. With the 

PFS-100 plugged in, the I/O 

reading is >50. When the 

PFS-100 is unplugged or the 

circuit loses power, this value 

drops below 10.

5. On the remote monitoring unit, 

click the Configuration icon, 

change the sensor label and 

click Save. Complete this step 

before installing additional 

sensors.

6. As data is analyzed over time, 

you can determine steady state   

conditions and set alarms 
accordingly.

Power Failure Sensor

Geist

TM

 PFS-100 Wiring Configuration

Remote monitoring unit

Analog Inputs 

C     1       2     3      C

Power source to 

be monitored

PFS-100

power 

adaptor

PFS-100

Black

Black 

striped