Vertiv™ eSure™ Power Extend Converter Mounting Bracket, Door, and Top Cover Kits Installation Manual
21
2.4
Installing the Power Extend Converter(s)
NOTE!
See also “Restrictions” on page 15.
Procedure
[ ] 1.
1-Row Cabinet Only
: Connect the return wire (P/N 564330) provided with the power extend converter to a power
extend converter return wire faston tab (P/N 565990) installed on the cabinet’s return bar in a previous step. See Figure
14. Repeat for each power extend converter to be installed.
Route the return wire (P/N 564330) connected above under the kit installed front mounting bracket. See Figure 14.
Repeat for each power extend converter to be installed.
[ ] 2.
2-Row Cabinet Only
: Connect the return wire (P/N 564330) and 4-inch long return wire jumper (P/N 565752) provided
with the power extend converter to a power extend converter return wire faston tab (P/N 565990) installed on the
cabinet’s return bar in a previous step. See Figure 15. Repeat for each power extend converter to be installed.
Route the return wire (P/N 564330) connected above behind the top-row distribution panel and under the kit installed
front mounting bracket (bottom-row). See Figure 15. Repeat for each power extend converter to be installed.
NOTE!
The return wire (P/N 564330) and 4-inch long return wire jumper (P/N 565752) may be connected to either the top
or bottom return bar.
NOTE!
The power extend converter is also furnished with an 8-inch long return wire jumper P/N 566207. The 8-inch long
return wire jumper is not used with this mounting bracket kit. It is used in other kits.