Unit Configuration
590-2172-501A/SL-29241/4200-136
8-1
8. Unit Configuration
8.1 Digital Input Configuration
Each digital input can be configured either for a voltage or contact closure input. Refer to the table
below.
Note
: Digital input configuration should only be performed by a qualified technician. Contact Technical
Support for details.
Mode
Acceptable Input Range
Voltage
> 4V = False
< 1V = True
Maximum nondestructive input: 60Vdc
Open/Close Contact
< 2K = True
Table 4 - Digital Input Modes
Seven jumpers for digital input and one jumper for RS-485 are supplied with the UXIMe for configuration.
There is a pair of 2-pin jumpers associated with each digital input, which must be set according to the
mode desired. The cover of the unit must be removed to gain access to these jumpers. Jumpers should
only be changed by a certified Vertiv technician. Refer to the following table and drawing to identify what
mode is required and where the jumpers are located.
Channel
Mode
Jumpers
Digital Input 1
Voltage
JP2 and JP3 are not installed
Open/Close Contact
JP2 and JP3 are installed
Digital Input 2
Voltage
JP4 and JP5 are not installed
Open/Close Contact
JP4 and JP5 are installed
Digital Input 3
Voltage
JP6 and JP8 are not installed
Open/Close Contact
JP6 and JP8 are Installed
Table 5 - Digital Input Jumper Settings