Vertiv™ NetSure™ Supervision Module for Distribution Unit Plus Installation and User Manual
11
4.7
NCU CAN Bus Connections
Refer to Figure 4.4.
Procedure (Connecting First Vertiv™ NetSure™ SM-DU+ Assembly to NCU)
1.
Connect the NetSure™ SM-DU+ assembly into the NCU CAN Bus. Connect CAN_H to CAN_H. Connect CAN_L to CAN_L.
Refer to the system documentation for NCU CAN port description and location. Cable P/N 562868 provided. Refer to Table
4.1 for cable information. Refer to Figure 4.4 for an interconnect diagram.
Table 4.1
CAN Bus Cable P/N 562868
Connector
Pin No.
Color
Signal Symbol
RJ-45
1
W/O
CAN_L
2
O
CAN_H
4*
BL
CAN_H
5*
W/BL
CAN_L
* For use with NetSure 8200 and NetSure 802 retrofit kits.
Procedure (Connecting Multiple NetSure™ SM-DU+ Assemblies Together)
NOTE!
The NCU can communicate with up to eight (8) NetSure™ SM-DU+ assemblies. Set each NetSure™ SM-DU+
assembly to a unique address number.
1.
To connect multiple NetSure™ SM-DU+ assemblies together, for all assemblies connect the CAN_H terminals together and
connect the CAN_L terminals together (CAN_H to CAN_H, CAN_L to CAN_L). See Figure 4.4 for an interconnect diagram.
2.
Connect a termination resistor such as P/N 561768 to the last NetSure™ SM-DU+ assembly in the NCU CAN bus. Connect to
CAN_H and CAN_L terminals along with the CAN_H and CAN_L leads factory connected to the terminal block. See
Figure 4.4.