10.6. Electrical Characteristics (Inverter Output)
Table 10-6
Inverter Output (To Critical Load)
Item
Unit
Rated Power (kVA)
80 kVA
Rated AC voltage
Vac
380/400/415 (Line voltage)
Frequency
Hz
50/60
Overload
%
For linear load requirement:
< 105%, continues;
105 ~ 110% of rated load, 60 min;
110 ~ 125% of rated load, 10 min;
125 ~ 150% of rated load, 1 min;
>
150%, 200 ms
Rated power factor
1
Crest factor
3:1
Voltage harmonic
distortion
%
<
1.5% (linear load); < 4.5% (non-linear load)
Dynamic response
recovery time
ms
40
Frequency
synchronization range
Hz
Rated frequency±3 Hz. Configurable range: ±0.5/±1/±2/±3/±10%
Frequency track rate
Hz/s
0.5 Hz/s. Configurable range: 0.1~3 Hz/s (single
UPS
), 0.6 Hz/s (parallel system)
Mains efficiency
%
Up to 96.2%
10.7. Electrical Characteristics (Bypass Input)
Table 10-7
Bypass Input
Item
Unit
Rated Power (kVA)
80 kVA
Rated AC voltage
Vac
380/400/415 (Line voltage)
Overload
Hz
< 110%, continues;
110 ~ 125% of rated load, 10 min;
125 ~ 150% of rated load, 1 min;
150, 200 ms
Frequency
%
50/60 (Range: 40~70)
Bypass voltage tolerance
Upper limit: +20%; settable: +10%, +15% or +20%; default: +15%
Lower limit: -40%; settable: -10%, -20%, -30% or -40%; default: -20%
Synchronisation window
Rated frequency ±3; ±0.5 ~ ±3 (optional)
Summary of Contents for EXS 0080kTK16FN01000
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...This page is intentionally left blank...
Page 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Page 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Page 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Page 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Page 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Page 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Page 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Page 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Page 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...