Operator Control and Display Panel
4.3. Prompt Window
When the system is in operation, a prompt window is displayed to alert about certain conditions and/or request
to confirm a command or other operation.
lists the prompts and the associated meanings.
Table 4-4 Prompts and Meanings
Prompt
Meaning
Incorrect password, please input again
This prompt appears when the user enters an incorrect Settings password
Operation failed, condition is not met
This prompt appears when the user attempts to execute a certain operation,
but the necessary condition is not met
Password changed OK
This prompt appears when the user has changed the Settings password
successfully
Fail to change password, please try again This prompt appears when the user attempts to change the Settings
password but has failed to use the same new password twice
Turn on failed, condition is not met
This prompt appears when the user presses the power button (or executes
the ‘Turn on/Turn off/to Bypass’ command on the ‘Control’ page)
Battery test abort, condition is not met
The battery self-test condition is not met. The user should verify that the
battery is in boost charge mode and the load capacity is larger than 20%
Equalize charge failed, Condition is not
met
This prompt appears when you select the Freshening charge command
while the battery freshening charge condition (such as no battery, charger
failure) is not met
Turn on more UPS to carry current load
The number of inverters already turned on is insufficient to carry the
existing load. The user is required to turn on more UPSs
The load is too high to be transferred
with interrupt
The total load must be less than the capacity of one UPS to allow a parallel
system to perform an interrupted transfer from bypass to inverter
Turn on local INV? OK or Cancel
This prompt appears when you press the power button, confirm or cancel it
Turn off local INV? OK or Cancel
This prompt appears when you press the power button, confirm or cancel it
Stop battery testing? OK or Cancel
This prompt appears when you select a command to stop battery test,
confirm or cancel it
New alarm presents, Show log? OK or
Cancel
This prompt appears when there is a new alarm generated, confirm or
cancel it
Start equalize charge? OK or Cancel
This prompt appears when you select a command of freshening charge,
confirm or cancel it
Stop equalize charge? OK or Cancel
This prompt appears when you select a command to stop freshening
charge, confirm or cancel it
Clear faults? OK or Cancel
This prompt appears when you select a command of fault clear, confirm or
cancel it
Battery reset? OK or Cancel
This prompt appears when you select a command of battery restore, confirm
or cancel it
Start capacity test? OK or Cancel
This prompt appears when you select a command of battery capacity test,
confirm or cancel it
Start maintaining test? OK or Cancel
This prompt appears when you select a command of battery maintenance
test, confirm or cancel it
Summary of Contents for EXS 0080kTK16FN01000
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...This page is intentionally left blank...
Page 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Page 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Page 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Page 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Page 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Page 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Page 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Page 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Page 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...