Vertiv | Liebert EXS 80kVA UPS | User Manual
108
Options
Table 9-7 Battery Control Port (X102)
BCB Box
Port
Communication Box
Port
Meaning
Signal State
DRV
BCB_DRIVE
Tripping control signal of BCB from the UPS
BCB tripping drive
Normal: 0 V
Tripping: 12 V
AUX
BCB_STATUS
Auxiliary contact of BCB
(contact off means BCB off)
Normal: 0 V, BCB closed;
Abnormal: open, BCB open
GND
GND
Signal ground
GND to GND
BCB_ONLINE BCB_ONLINE
BCB online state
To GND by default
• The cable of the J2 BCB port must be routed separately from the power cable. It uses the dual-insulat-
ed shielded cable (the CSA is generally 0.5 mm
2
~ 1 mm
2
when the max. wiring distance is 30 m), and
the UPS side of the shielding coat must be connected to the enclosure reliably.
Caution
If the corresponding functions are not required, just do not connect corresponding terminals.
9.6. Battery Cabinet
The BCB cabinet contains batteries, BCB and a BCB control board.
Vertiv provides the BCB cabinet for battery backup use. Refer to
for description of the BCB
cabinet and its data.
The BCB cabinet protects the battery against overdischarge and overcurrent, and also isolates the UPS and
battery, thus reducing the risk at lowest for service personnel during the maintenance. The cabinet inside has
connection bars for connecting the cables from the UPS.
• The signal cables from the UPS to the BCB control board must be routed in a separate cable trough and
separated from battery power cables.
Summary of Contents for EXS 0080kTK16FN01000
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...This page is intentionally left blank...
Page 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Page 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Page 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Page 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Page 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Page 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Page 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Page 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Page 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...