VC41LDVI/VC41CDVI Gas Fireplace Insert

7

GeNeRAL INSTALLATION INFORMATION  

BeFORe yOu START

Read this homeowner manual thoroughly and follow all 

instructions  carefully.  Inspect  all  contents  for  shipping 

damage and immediately inform your dealer if any damage 

is found. Do not install any unit with damaged, incomplete, 

or substitute parts. Check your packing list to verify that all 

listed parts have been received.
The following factors should be taken into consideration:

  This insert should have sufficient access for its safe 

operation and maintenance.

  The flow of combustion and ventilation air must not be 

obstructed.

  Minimum clearances to combustibles, such as mantels, 

must be maintained. 

Refer to Pages 8 and 9, Figures 

3, 4 and 5.

  Never obstruct the front opening of the insert.

  Do  not  install  in  the  vicinity  where  gasoline  or  other 

flammable liquids may be stored.

  These  units  can  be  installed  in  a  bedroom.  Refer  to 

National Fuel Gas Code ANSI Z233.1/NFPA 54 (current 

edition),  the  Uniform  Mechanical  Code  (current  edi-

tion), and Local Building Codes for specific installation 

requirements.

IMPORTANT: your direct vent insert was designed to 

be installed in an existing wood burning fireplace. The 

location and clearances are subject to local building 

codes

.

CLeARANCeS
MINIMuM FIRePLACe SIZe/CLeARANCeS 

TO COMBuSTIBLeS

W

ARNING

The dimensions shown on 

Pages 8 and 9, 

Figures 3 and 4

, are minimum clearances to 

maintain when installing this heater. Follow 

these instructions carefully to ensure safe 

installation.  Failure  to  follow  instructions 

exactly can create a fire hazard.

INSeRT APPLICATIONS

Before  installing  the  gas  fireplace  insert,  consider  the 

functioning needs of the fireplace. Confirm the size of the 

fireplace cavity, the design of the chimney, and the avail-

ability of the gas supply and electricity for the insert fan.

IMPORTANT: your  direct  vent  insert  is  designed  to 

be  only  vented  vertically  with  a  minimum  height  of 

10 feet.

When the unit is installed into a wood burning fireplace, 

the minimum distance the mantel can be placed above the 

fireplace is governed by local building codes applicable to 

wood burning fireplaces. Consult local authorities having 

jurisdiction  for  these  clearances. The  underside  of  the 

mantel will become warm. Use only finishes which are heat 

resistant and do not discolor.

Summary of Contents for VC41CDVINTSC

Page 1: ...G Improper installation adjustment alteration services or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer se...

Page 2: ...as Shutoff Tool 19 Electrical Installation 20 Electrical Wiring 20 Log Placement 21 Decorative Glass Installation 24 Bead Placement 24 Stone Placement 25 Operating Instructions 26 For Your Safety Read...

Page 3: ...installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the fl...

Page 4: ...from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Cana...

Page 5: ...rtified without deration for elevations up to 4 500 feet 1 370 m above sea level For elevations above 4 500 feet 1 370 m in USA installation must be in accordance with the current ANSI Z223 1 NFPA 54...

Page 6: ...ireplace Insert insert dimensions Figure 2 VC41LDVI Fireplace Insert Dimensions 24 6QE 621 mm 1356M 337 mm 1256O 318 mm 2 6QE 56 mm 55 6QE 144 mm 1856 460 mm 26 6QE 668 mm 2956 740 mm 256M 57 mm 2356Q...

Page 7: ...specific installation requirements IMPORTANT Your direct vent insert was designed to be installed in an existing wood burning fireplace The location and clearances are subject to local building codes...

Page 8: ...it is considered a mantel and must meet the mantel requirements listed in this manual FP2988 Figure 3 Mantel Clearances NOTE Side clearance to combustibles is 10 254 mm from opening whether it is sid...

Page 9: ...AND CENTER BRACKET In order to fit insert into a smaller opening the command center bracket may be removed Refer to Pages 6 and 9 for dimensions If the bracket is removed the small 2 deep three sided...

Page 10: ...well ventilated OPEN ALL WINDOWS DURING INITIAL BURN OFF CURING PHASE Burn your insert for at least six 6 hours on HIGH the first time you use it Place the fan in the OFF position during this time Fp...

Page 11: ...ore attempting installation Failure to do so could result in serious injury property damage or loss of life Operation of improperly installed and maintained venting system could result in serious inju...

Page 12: ...d to resize orifice for use at high altitude contact your dealer High Temp Silicone FP2948 exhaust pipe 3 and 3 UL 1777 Gas Liner Apply high temperature silicone to lines on both ends and secure with...

Page 13: ...let Recommended block off plate noncombustible metal Prevents odors from chimney entering room UL 127 Solid Fuel Z C Fire box Figure 11 Inlet and Exhaust Reline NOTE You may use a reline configuration...

Page 14: ...els and retainers from packaging 2 Remove two 2 screws on each side of front edge of chamber 3 Install one 1 front brick retainer bracket on each side with the screws removed in Step 2 4 Carefully set...

Page 15: ...celain Panel Kit Contemporary Porcelain Panel Kit Contemporary Support Bracket Supplied w Contem porary Kit Use Self tapping Screws Existing Support Figure 14 1 Remove porcelain panels and hardware fr...

Page 16: ...e closed Retighten screws NOTE For propane LP units the baffle assembly is com pletely removed for venting under 20 ft 6 m For venting 20 ft and above the baffle assembly is to be used with only one 1...

Page 17: ...ou must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regula tor damage could occur Install external regulator with the ven...

Page 18: ...contaminants This keeps them from going into the burner system gas con trols If sediment trap drip leg is not installed or is installed wrong burner system may not run properly NOTE The gas line conn...

Page 19: ...ater and soap solution or a gas sniffer 4 To check gas pressures at valve turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point Turn unit to high F...

Page 20: ...electrical supply Electricity is only needed to operate blower Verify proper operation after servicing Electrical connections should only be performed by a qualified licensed electrician Main power mu...

Page 21: ...rs may be added to entire burner area in front of grate to hide burner and log support brackets Figure 23 Ember Material Area The positioning of the logs is critical to the safe and clean operation of...

Page 22: ...pport bracket Figure 24 Figure 25 4 Install log 2 by placing locator block between front and rear burner Place notch in bottom of log on the back end of the 2nd from left grate tine Figure 25 Log 3 LG...

Page 23: ...g 5 by placing rectangu lar notch on the bottom of the log onto the rectangular protrusion in the center of log 1 Place the front of log 5 onto the grate bar to the right of the center grate tine Push...

Page 24: ...d with unit 2 Mix the two 2 bags of decorative glass provided in the kit as desired Lay glass on top of burner and cover burner area with one 1 layer Glass may be used around the perimeter next to the...

Page 25: ...Lay glass on top of burner and cover burner area with one 1 layer Glass may be used around the perimeter next to the wall Make sure glass is not blocking gaps between perimeter bracket and the burner...

Page 26: ...one Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not fun...

Page 27: ...s go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will lig...

Page 28: ...de and rear brick panels 2 Remove log support bracket by removing two 2 screws in rear and one 1 screw on each side wall FP1940 air shutter part open Air Shutter FP1940 Figure 32 Push Adjustment Lip U...

Page 29: ...just below the horizontal grate bar The slide adjustable air shutter has a range of 1 Figure 34 To increase air mixture open the slide adjustment by gently pulling on the lever When lever stops it ha...

Page 30: ...X Low battery Indication for Transmitter X Child Proof Lock out X LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blowe...

Page 31: ...3 seconds when the master switch Shutoff on the main burner is off RF Remote Receiver Push the RF receiver On Off button on the control board RF OFF On Off Beep once for ON and beep twice for OFF Lear...

Page 32: ...Learning GREEN Flashes every 1 sec for 10 sec AC Power On GREEN solid Pressure Switch Failed Power Vent only One RED every 2 sec until manual reset Self Diagnostics Chart The Command Center has a self...

Page 33: ...arrows The blue LED backlight lights up for 8 seconds when any of the touch buttons is pressed The menus include TIMER THERMO LIGHT FAN and AUX Rear Burner Control The adjustment arrows include ON up...

Page 34: ...on the Command Cen ter will flash for 10 seconds 4 During the 10 sec onds press the OFF button on the transmitter to learn Another two beeps will be given to confirm a success ful learning Figure 40 T...

Page 35: ...ireplace will be shut down completely when the timer counts down to zero 6 To exit Timer Mode a Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to z...

Page 36: ...d OFF down button to increase de crease the blower speed 3 Press the fan button again to confirm the speed set ting If the fireplace is on the blower speed will take effect right away if the fireplace...

Page 37: ...ng is A touch any place in the touch area to bring up the icons then press TIMER but ton and THERMO button at the same time for 3 sec onds The backlight will flash once to indicate that the setting ha...

Page 38: ...play is blank 2 Check battery installation or replace batteries 3 LCD display shows funny display 3 Reset the transmitter see Resetting the Transmitter section 4 Appliance does not come on 2 The trans...

Page 39: ...not use abrasive cleaners They will damage the glass surface pilot and burner flames Visually check pilot and burner flames periodically Refer to Figure 50 for typical burner flame Refer to Figure 51...

Page 40: ...Contact dealer where you bought heater 4 Remove rock wool Clean burner and burner ports Figure 53 5 Replace log set and ember according to instructions on Pages 21 25 Replace decorative glass accordi...

Page 41: ...through Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery C...

Page 42: ...20304685 VC41LDVI VC41CDVI Gas Fireplace Insert REPLACEMENT PARTS 24 6 1 2 3 4 5 11 12 14 16 39 32 34 33 38 4685 VC41LDVI parts 17 27 25 26 31 30 29 10 7 8 9 13 15 18 19 20 21 22 11 19 23 40 47 48 8...

Page 43: ...nd Center SCS 1 80D0005 80D0005 80D0005 27 AC Module SCS 1 80D0004 80D0004 80D0004 28 Remote Control 1 TSFRSC TSFRSC TSFSC 29 Wire Valve Control Board SCS 1 80D0010 80D0010 80D0010 30 Wire CC CB 24 SC...

Page 44: ...nversion Kits Natural Gas to LP VC41LDVINTSC Kit 40ICFPGK VC41CDVINTSC Kit ICF40LPK WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically ap...

Page 45: ...TVI 5b Glass Frame Textured Mocha ICF40GTTM 6a Rectangular Double Door Satin Black ICF40R2DSB 6b Rectangular Double Door Vintage Iron ICF40R2DVI 6c Rectangular Double Door Textured Mocha ICF40R2DTM 7a...

Page 46: ...comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Plea...

Page 47: ...ited 10 year warranty will be void if the appliance is not installed by a qualified installer in accor dance with the installation instructions The limited 10 year warranty will also be void if the ap...

Page 48: ...ndement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 Efficiency Ratings Model EnerGuide Ratings D O E Fireplace Efficiency AFUE VC41LDVINTSC 75 8 70 67 VC41LDVIPTSC 78 9 71 26 VC41CDVINTSC 7...

Reviews: