Vermont Castings • Intrepid II Installation & Operating Manual_R48 • 11/17
3-90-2000966
Distance from the Center of the Flue Collar to the Wall in Top-Exit Installations
The information on this page is helpful in planning stove placement for top-exiting installations, particularly those installations
with chimneys that pass through the ceiling. However, this is not a clearance chart. Final stove clearances must adhere to
the guidelines stated in the clearance charts located on the previous pages.
Intrepid II: WITH Stove and Chimney Connector Heat Shields
Unprotected Surfaces
Protected Surfaces
Parallel Installations
Corner
Installations**
Parallel Installations
Corner
Installations**
Side (A)
Rear (B)
Corner (C)
Side (D)
Rear (E)
Corner (F)
34-3/4" (883mm)
15" (381mm)
18-3/4" (476mm)
22-3/4" (578mm)
8" (203mm)
16-3/4" (426mm)
** To locate center of flue collar for corner installation, add 7" (180mm) to the clearance distance form stove corner to wall. Mark off the resulting
distance from the corner along both walls. Next, measure the same distance form these two points out from the walls. These last two measurements
will meet at a point representing the center of the flue collar. Refer to the diagrams above.
ST511a
Intrepid
flue centerline
Diagrams
11/16/00
A
B
C
D
E
F
Intrepid II: WITHOUT Stove and Chimney Connector Heat Shields
Unprotected Surfaces
Protected Surfaces
Parallel Installations
Corner
Installations**
Parallel Installations
Corner
Installations**
Side (A)
Rear (B)
Corner (C)
Side (D)
Rear (E)
Corner (F)
34-3/4" (883mm)
29" (737mm)
26-3/4" (680mm)
22-3/4" (578mm)
15" (381mm)
16-3/4" (426mm)
ST51
Intrepid
flue centerline
Diagrams
11/16/00
*
A
B
C
*
D
E
F
*This distance, from the center of the flue collar to the front edge of the hearth, is the same for all installations on this page: 31" in the United States
and 33" (840mm) in Canada.